| Plan Review Notes For Permit 02102235 |
| Permit Number |
02102235 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-13 00:00:00 | DENIED; | | | PAGE A-16. PLUMBING RISER DIAGRAMS. | | | UNIT "A" AND "B" | | | 1.MASTER W/C 3" WET VENT REQUIRED. SEE | | | FBC PLUMBING TABLE 908.3. | | | 2.KITCHEN BRANCH. 2" DRY VENT NOT | | | REQUIRED. | | | 3.RISERS ARE GOING TO WRONG APARTMENTS. | | | "A" SHOULD GO TO "C" ECT. | | | 4.FLOOR PLAN SHOWS L.T.S ON FIRST FLOOR | | | NONE SHOWN ON RISER DIAGRAMS. | | | UNITS "C" AND "D" | | | 1.RISER DIAGRAM SHOWS 2 WASHERS FLOOR | | | PLAN SHOWS ONE. | | | 2.MASTER W/C WET VENT REQUIRED TO BE 3" | | | SEE TABLE 908.3. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|