Plan Review Notes
Plan Review Notes For Permit 02102235
Permit Number 02102235
Review Stop P
Sequence Number 1
Notes
Date Text
2002-11-13 00:00:00DENIED;
 PAGE A-16. PLUMBING RISER DIAGRAMS.
 UNIT "A" AND "B"
 1.MASTER W/C 3" WET VENT REQUIRED. SEE
 FBC PLUMBING TABLE 908.3.
 2.KITCHEN BRANCH. 2" DRY VENT NOT
 REQUIRED.
 3.RISERS ARE GOING TO WRONG APARTMENTS.
 "A" SHOULD GO TO "C" ECT.
 4.FLOOR PLAN SHOWS L.T.S ON FIRST FLOOR
 NONE SHOWN ON RISER DIAGRAMS.
 UNITS "C" AND "D"
 1.RISER DIAGRAM SHOWS 2 WASHERS FLOOR
 PLAN SHOWS ONE.
 2.MASTER W/C WET VENT REQUIRED TO BE 3"
 SEE TABLE 908.3.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369