Plan Review Notes
Plan Review Notes For Permit 02102235
Permit Number 02102235
Review Stop M
Sequence Number 1
Notes
Date Text
2002-11-30 00:00:00PLAN DENIED
 1) DESIGN TO 2001 MECHANICAL CODE
 2) VARIFY TYPE OF VENTILATION USED FOR
 FRESH AIR NATURAL SECTION 402 OR
 MECHANICAL SECTION 403
 3) NEED CALCULATION FOR TYPE OF
 VENTILATION USED
 4) REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 5)REFER TO SECTION 606 SMOKE DETECTION
 SYSTEM CONTROL
 6) SOME DUCT SIZE MISSING ON PLANS
 7) CONDENSATE LINE MUST TERMINATE 12IN.
 FROM BUILDING FBC.SECTION 1503.4.4
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390