| Plan Review Notes For Permit 02102235 |
| Permit Number |
02102235 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-30 00:00:00 | PLAN DENIED | | | 1) DESIGN TO 2001 MECHANICAL CODE | | | 2) VARIFY TYPE OF VENTILATION USED FOR | | | FRESH AIR NATURAL SECTION 402 OR | | | MECHANICAL SECTION 403 | | | 3) NEED CALCULATION FOR TYPE OF | | | VENTILATION USED | | | 4) REFER TO SECTION 601.4 BALANCED | | | RETURN AIR | | | 5)REFER TO SECTION 606 SMOKE DETECTION | | | SYSTEM CONTROL | | | 6) SOME DUCT SIZE MISSING ON PLANS | | | 7) CONDENSATE LINE MUST TERMINATE 12IN. | | | FROM BUILDING FBC.SECTION 1503.4.4 | | | PLAN REVIEW BY HAROLD MOSER | | | (561)659-8096 EXT.8390 |
|