| 2002-12-11 00:00:00 | BUILDING DENIED |
| | |
| | NOTE: IMPACT FEES, SURVEY AND NOTICE OF |
| | COMMENCEMENT WILL BE REQUIRED FOR EACH |
| | BUILDING APPLIED FOR UNDER THE MASTER. |
| | |
| | 1) INDICATE THE INTERNAL PRESSURE |
| | COEFFICENT ON C1. IT IS + OR - 0.18 FOR |
| | AN ENCLOSED STRUCTURE. |
| | |
| | 2) PLEASE REVISE PLAN NOTE #11 ON C1, |
| | HURRICANE SHUTTERS ARE REQUIRED IN WPB, |
| | WHICH IS IN THE WIND BORN DEBRIS REGION, |
| | BUT NOT IN THE HVHZ. FBC 1606.1.4 |
| | |
| | 3)REVISE THE NOTES ON A3 ON THE REQUIRED |
| | APPROVED CLOSERS TO REFERENCE THE 2001 |
| | FLORIDA BUILDING CODE. |
| | |
| | 4) THE C LABEL DESIGNATIONS FOR FIRE |
| | RATED DOORS IS NO LONGER USED. SEE FBC |
| | 705.1.3.2.1. SPECIFY 3/4 HOUR RATED FIRE |
| | DOORS ON PLANS WHERE REQUIRED PER FBC |
| | TABLE 705.1.2. |
| | |
| | 5) THE WALL BELOW AND THE UNDERSIDE OF |
| | THE STAIRS ARE REQUIRED TO HAVE A ONE |
| | HOUR FIRE RATING. PLEASE INDICATE THIS |
| | ON FLOOR PLAN ON A3. |
| | |
| | 6) THE CLOSET DOORS IN BEDROOMS #2 OF |
| | UNIT A, #3 OF UNIT D AND #3 OF UNIT C |
| | MUST PROVIDE A 32"NOMINAL CLEAR OPENING |
| | IN ORDER FOR THE USER TO PASS THROUGH TO |
| | ACCESS THE CONTENTS IS REQUIRED BY THE |
| | FAIR HOUSING ACT. |
| | |
| | 7) THE DOUBLE DOORS TO THE DEN IN UNITS |
| | D AND A, MUST HAVE BOTH LEAFS ACTIVE OR |
| | THE ONE ACTIVE LEAF MUST PROVIDE A 32" |
| | CLEAR OPENING PER FAIR HOUSING ACT. |
| | INDICATE ON THE PLANS ON SHEETS A3 AND |
| | A4 & FOR OPTIONS Q2,Q3,D2,D3 ON A17 AND |
| | A18. |
| | |
| | 8) THE MASTER BATH W/C OPTIONS Q1,S1,M2 |
| | AND D1 ON SHEETS A17 AND A18 DO NOT |
| | COMPLY WITH FAIR HOUSING REQUIREMENTS. |
| | |
| | 9) INDICATE THE CLEAR FLOOR SPACE |
| | DIMENSIONS AT THE BATHROOM FIXTURES WITH |
| | SHADED AREAS. |
| | |
| | 10) THE PROJECT TITLE BLOCK ON THE PLANS |
| | ARE INCORRECT. PLEASE REVISE. |
| | |
| | 11)ON SHEET A4 SECTIONS A,B,C ARE TAGGED |
| | AS BEING LOCATED ON A6, BUT ARE ON A7. |
| | SECTIONS 1,3 AND 5 ARE MARKED AS BEING |
| | ON A7, BUT ARE LOCATED ON A8. PLEASE |
| | CORRECT. |
| | |
| | 12) SHEET A5 AND A6 HAVE A NOTE THAT |
| | INDICATES STUCCO OVER CONCRETE BLOCK AT |
| | THE EXTERIOR WALLS ABOVE THE GARAGE, |
| | WHICH ARE WOOD FRAME. PLEASE CORRECT. |
| | |
| | 13) REVISE THE HANDRAIL AND PARTY WALL |
| | NOTES ON A7 TO REFERENCE THE 2001 FBC. |
| | |
| | 14) REVISE THE ATTIC VENTILATION NOTES |
| | ON A10 TO REFERENCE THE 2001 FBC. |
| | |
| | 15) PROVIDE A DETAIL OF THE STAIRS THAT |
| | INDICATES THE RISER AND TREAD DIMENSIONS |
| | AND SHOWS COMPLIANCE WITH FBC 1007.3. |
| | |
| | 16) PROVIDE DETAILS OF THE INTERIOR |
| | GUARDRAIL AT THE TOP OF THE STAIRS AND |
| | IN FRONT OF THE ELEVATOR. INDICATE THE |
| | ATTACHMENTS, DIMENSIONS, ETC. SEE FBC |
| | 1015. |
| | |
| | 17) THE KEY PLANS AND INSTALLATION |
| | SCHEDULES FOR THE STORM PANELS DO NOT |
| | CORRESPOND WITH THE PLANS. A WRITTEN |
| | STORM PANEL STORAGE AND INSTALLATION |
| | PLAN MUST BE SUBMITTED AND APPROVED BY |
| | THE BUILDING OFFICIAL. |
| | |
| | 18) THE ENERGY CALCULATIONS ARE REQUIRED |
| | TO BE SIGNED BY THE OWNER/AGENT. THE |
| | CONDITIONED FLOOR AREA ON THE ENERGY |
| | CALCS. DOES NOT MATCH THE CONDITIONED |
| | AREA GIVEN ON THE PLANS. |
| | |
| | 19) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - OUTSWING DOORS W/SIDELITES (EXPIRED) |
| | - STRUCTURAL MULLIONS (EXPIRED) |
| | - SLIDING GLASS DOORS (BOTH ARE EXPIRED) |
| | - OVERHEAD GARAGE DOOR(DRAWING SUBMITTED |
| | IS FOR DOOR WITH MAXIMUM WIDTH OF 9') |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |