2002-12-11 00:00:00BUILDING DENIED
  
 NOTE: IMPACT FEES, SURVEY AND NOTICE OF
 COMMENCEMENT WILL BE REQUIRED FOR EACH
 BUILDING APPLIED FOR UNDER THE MASTER.
  
 1) INDICATE THE INTERNAL PRESSURE
 COEFFICENT ON C1. IT IS + OR - 0.18 FOR
 AN ENCLOSED STRUCTURE.
  
 2) PLEASE REVISE PLAN NOTE #11 ON C1,
 HURRICANE SHUTTERS ARE REQUIRED IN WPB,
 WHICH IS IN THE WIND BORN DEBRIS REGION,
 BUT NOT IN THE HVHZ. FBC 1606.1.4
  
 3)REVISE THE NOTES ON A3 ON THE REQUIRED
 APPROVED CLOSERS TO REFERENCE THE 2001
 FLORIDA BUILDING CODE.
  
 4) THE C LABEL DESIGNATIONS FOR FIRE
 RATED DOORS IS NO LONGER USED. SEE FBC
 705.1.3.2.1. SPECIFY 3/4 HOUR RATED FIRE
 DOORS ON PLANS WHERE REQUIRED PER FBC
 TABLE 705.1.2.
  
 5) THE WALL BELOW AND THE UNDERSIDE OF
 THE STAIRS ARE REQUIRED TO HAVE A ONE
 HOUR FIRE RATING. PLEASE INDICATE THIS
 ON FLOOR PLAN ON A3.
  
 6) THE CLOSET DOORS IN BEDROOMS #2 OF
 UNIT A, #3 OF UNIT D AND #3 OF UNIT C
 MUST PROVIDE A 32"NOMINAL CLEAR OPENING
 IN ORDER FOR THE USER TO PASS THROUGH TO
 ACCESS THE CONTENTS IS REQUIRED BY THE
 FAIR HOUSING ACT.
  
 7) THE DOUBLE DOORS TO THE DEN IN UNITS
 D AND A, MUST HAVE BOTH LEAFS ACTIVE OR
 THE ONE ACTIVE LEAF MUST PROVIDE A 32"
 CLEAR OPENING PER FAIR HOUSING ACT.
 INDICATE ON THE PLANS ON SHEETS A3 AND
 A4 & FOR OPTIONS Q2,Q3,D2,D3 ON A17 AND
 A18.
  
 8) THE MASTER BATH W/C OPTIONS Q1,S1,M2
 AND D1 ON SHEETS A17 AND A18 DO NOT
 COMPLY WITH FAIR HOUSING REQUIREMENTS.
  
 9) INDICATE THE CLEAR FLOOR SPACE
 DIMENSIONS AT THE BATHROOM FIXTURES WITH
 SHADED AREAS.
  
 10) THE PROJECT TITLE BLOCK ON THE PLANS
 ARE INCORRECT. PLEASE REVISE.
  
 11)ON SHEET A4 SECTIONS A,B,C ARE TAGGED
 AS BEING LOCATED ON A6, BUT ARE ON A7.
 SECTIONS 1,3 AND 5 ARE MARKED AS BEING
 ON A7, BUT ARE LOCATED ON A8. PLEASE
 CORRECT.
  
 12) SHEET A5 AND A6 HAVE A NOTE THAT
 INDICATES STUCCO OVER CONCRETE BLOCK AT
 THE EXTERIOR WALLS ABOVE THE GARAGE,
 WHICH ARE WOOD FRAME. PLEASE CORRECT.
  
 13) REVISE THE HANDRAIL AND PARTY WALL
 NOTES ON A7 TO REFERENCE THE 2001 FBC.
  
 14) REVISE THE ATTIC VENTILATION NOTES
 ON A10 TO REFERENCE THE 2001 FBC.
  
 15) PROVIDE A DETAIL OF THE STAIRS THAT
 INDICATES THE RISER AND TREAD DIMENSIONS
 AND SHOWS COMPLIANCE WITH FBC 1007.3.
  
 16) PROVIDE DETAILS OF THE INTERIOR
 GUARDRAIL AT THE TOP OF THE STAIRS AND
 IN FRONT OF THE ELEVATOR. INDICATE THE
 ATTACHMENTS, DIMENSIONS, ETC. SEE FBC
 1015.
  
 17) THE KEY PLANS AND INSTALLATION
 SCHEDULES FOR THE STORM PANELS DO NOT
 CORRESPOND WITH THE PLANS. A WRITTEN
 STORM PANEL STORAGE AND INSTALLATION
 PLAN MUST BE SUBMITTED AND APPROVED BY
 THE BUILDING OFFICIAL.
  
 18) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT. THE
 CONDITIONED FLOOR AREA ON THE ENERGY
 CALCS. DOES NOT MATCH THE CONDITIONED
 AREA GIVEN ON THE PLANS.
  
 19) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - OUTSWING DOORS W/SIDELITES (EXPIRED)
 - STRUCTURAL MULLIONS (EXPIRED)
 - SLIDING GLASS DOORS (BOTH ARE EXPIRED)
 - OVERHEAD GARAGE DOOR(DRAWING SUBMITTED
 IS FOR DOOR WITH MAXIMUM WIDTH OF 9')
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202