| Notes |
| Date |
Text |
| 2003-04-08 00:00:00 | ********* UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST | | | REVIEW/REDLINED. | | | PLEASE SIZE AWG/OCP FOR AHU #2. 10KW W/ | | | #10 AND 2P-25. | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210-52 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|