| 2003-05-15 00:00:00 | ************ UNSAT ************** |
| | |
| | PLEASE SEE COMMENTS FROM PREVIOUS REVIEW |
| | |
| | 1)NOTE: PLEASE SEE RISER DIAGRAM,THE |
| | COTTAGE UNIT #`S DO NOT CORRELATE WITH |
| | UNIT #`S SHOWN ON UPPER LEFT HAND |
| | CORNER OF PANEL SCHEDULE? |
| | PLEASE ALSO CLARIFY WHY THERE ARE TWO- |
| | -SETS OF 250 MCM FOR A 200A MCB PANEL |
| | AND CLARIFY HOW TWO 250MCM WILL FIT INTO |
| | A MCB? IF MAC ADAPTERS ARE TO BE USED |
| | PLEASE ADD NOTE. 215-5 |
| | |
| | 2)NOTE: PLEASE SEE LOAD CALCULATIONS, |
| | ON PANEL SCHEDULE. LOADS ARE INCOMPLETE |
| | FOR PANEL. SHOWN MOSTLY AS BLANK. |
| | THE LOAD CALCULATIONS ON BOTTOM RIGHT |
| | HAND CORNER OF SHEET E7-4.01 ARE FOR |
| | SFR/DWELLING. PLEASE NOTE, CALCS NEED |
| | TO BE DONE UNDER COMM USE AND SHOW ALL |
| | CONTINUOUS LOADS AT 125%, WHICH WAS |
| | STARTED ON PANEL SCHEDULE? |
| | 215-5,215-3, 230-42,220-10,11,13,03,, |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE REMOVE OLD/VOIDED SHEETS |
| | AND INSERT NEW INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | PLEASE SEE LETTER ATTACHED FOR DESIGN |
| | OF RECORD. FS 553.80(2)(B) |
| | |
| | PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |