Plan Review Notes
Plan Review Notes For Permit 02102207
Permit Number 02102207
Review Stop M
Sequence Number 2
Notes
Date Text
2003-04-11 00:00:00DENIED:COTTAGES 6 - 13
  
 1.PLAN SHEET A6-2.1 & A7-2.1, LAUNDRY
 ROOM NOW HAS A 1 HR SEPARATION.PLEASE
 PROVIDE FIRE DAMPERS ON THE 14" X 14"
 SUPPLY & RETURN DUCT THAT RUNS THROUGH
 THIS DUCT.
  
 2.DUCTS THAT ARE DO NOT EXCEED 100 SQ
 INCHES ARE NOT REQUIRED TO HAVE FIRE
 DAMPERS IF THE DUCT IS A MINIMUM OF
 .0217" STEEL & HAS NO DUCT OPENINGS FOR
 NOT LESS THAN 5 FT FROM RATED WALL.
 PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPER ON THE
 JOBSITE AT TIME OF INSPECTION.