| Plan Review Notes For Permit 02102207 |
| Permit Number |
02102207 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-11 00:00:00 | DENIED:COTTAGES 6 - 13 | | | | | | 1.PLAN SHEET A6-2.1 & A7-2.1, LAUNDRY | | | ROOM NOW HAS A 1 HR SEPARATION.PLEASE | | | PROVIDE FIRE DAMPERS ON THE 14" X 14" | | | SUPPLY & RETURN DUCT THAT RUNS THROUGH | | | THIS DUCT. | | | | | | 2.DUCTS THAT ARE DO NOT EXCEED 100 SQ | | | INCHES ARE NOT REQUIRED TO HAVE FIRE | | | DAMPERS IF THE DUCT IS A MINIMUM OF | | | .0217" STEEL & HAS NO DUCT OPENINGS FOR | | | NOT LESS THAN 5 FT FROM RATED WALL. | | | PROVIDE MANUFACTURERS INSTALLATION | | | INSTRUCTIONS FOR THE FIRE DAMPER ON THE | | | JOBSITE AT TIME OF INSPECTION. |
|