| 2003-03-28 00:00:00 | ************* NOTES/UNSAT ********** |
| | #6,8,11,13 |
| | 1)NOTE: PLEASE SEE RISER DIAGRAM/PANEL |
| | SCHEDULE AND LOAD CALCUALTIONS. |
| | LOAD CALCS SHOW PANEL TO BE 250 MLO W/ |
| | 250A MCB, PANEL SCHEDULE SHOWS 200A MCB, |
| | PLEASE CLARIFY AND CORRELATE. |
| | |
| | 2)NOTE: PLEASE CLARFIY LOAD CALCAULTIONS |
| | LOAD CALCS ON PANEL SCHEDULE ARE SHOWN |
| | AS COMM AND OTHER LOAD CALCS SHOWN AS |
| | RESIDENTIAL?? |
| | MIXED USE |
| | |
| | 3)NOTE: PLEASE NOTE, PLANS UNDER THIS |
| | PERMIT # SHOWS PANEL 6L/A ON RISER AND |
| | 7L/A ON PANEL SCHEDULE AND SHOWS TYP FOR |
| | 9,10 AND 11. TITLE BLOCK ON RIGHT SHOWS |
| | TYPICAL FOR #`S 6,8,11,13? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER. |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | [email protected] |
| | ********NOTES FOR 7,9,10,12 ******* |
| | |
| | PLEASE SEE OTHER NOTES FOR COTTAGES |
| | SOME NOTES ARE THE SAME. |
| | |
| | 1)NOTE: PLEASE CLARFIFY HOW/WHERE |
| | SERVICE SIZE CHANGES? RISER SHOWS |
| | SEC`S CHANGING TO TWOS SETS OF 250 MCM |
| | FOR 8,9,12 &13? |
| | PLEASE NOTE, TWO SETS OF 250MCM ARE |
| | RATED FOR 510A`S? PLEASE CLARIFY. |
| | PANELS ARE SHOWN AT 200A MC AND LOAD |
| | CALCS AT BOTTOM SHOW 250 OCP FOR 250A |
| | PANEL?? |
| | PLEASE SEE TITLE BLOCK SHOWS TYPICAL |
| | AS UNITS/ 7,9,10 &12 AND ABOVE PANEL, |
| | TYPICAL SHOWS 8,12,13?? |
| | |
| | PLEASE CORRELATE. PLEASE SUBMIT FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |