Plan Review Notes
Plan Review Notes For Permit 02102207
Permit Number 02102207
Review Stop E
Sequence Number 2
Notes
Date Text
2003-03-28 00:00:00************* NOTES/UNSAT **********
 #6,8,11,13
 1)NOTE: PLEASE SEE RISER DIAGRAM/PANEL
 SCHEDULE AND LOAD CALCUALTIONS.
 LOAD CALCS SHOW PANEL TO BE 250 MLO W/
 250A MCB, PANEL SCHEDULE SHOWS 200A MCB,
 PLEASE CLARIFY AND CORRELATE.
  
 2)NOTE: PLEASE CLARFIY LOAD CALCAULTIONS
 LOAD CALCS ON PANEL SCHEDULE ARE SHOWN
 AS COMM AND OTHER LOAD CALCS SHOWN AS
 RESIDENTIAL??
 MIXED USE
  
 3)NOTE: PLEASE NOTE, PLANS UNDER THIS
 PERMIT # SHOWS PANEL 6L/A ON RISER AND
 7L/A ON PANEL SCHEDULE AND SHOWS TYP FOR
 9,10 AND 11. TITLE BLOCK ON RIGHT SHOWS
 TYPICAL FOR #`S 6,8,11,13?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]
 ********NOTES FOR 7,9,10,12 *******
  
 PLEASE SEE OTHER NOTES FOR COTTAGES
 SOME NOTES ARE THE SAME.
  
 1)NOTE: PLEASE CLARFIFY HOW/WHERE
 SERVICE SIZE CHANGES? RISER SHOWS
 SEC`S CHANGING TO TWOS SETS OF 250 MCM
 FOR 8,9,12 &13?
 PLEASE NOTE, TWO SETS OF 250MCM ARE
 RATED FOR 510A`S? PLEASE CLARIFY.
 PANELS ARE SHOWN AT 200A MC AND LOAD
 CALCS AT BOTTOM SHOW 250 OCP FOR 250A
 PANEL??
 PLEASE SEE TITLE BLOCK SHOWS TYPICAL
 AS UNITS/ 7,9,10 &12 AND ABOVE PANEL,
 TYPICAL SHOWS 8,12,13??
  
 PLEASE CORRELATE. PLEASE SUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]