| 2002-12-16 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) PER SECTION 11-9.1.1, ALL PUBLIC USE |
| | AND COMMON USE AREAS ARE REQUIRED TO BE |
| | DESIGNED AND CONSTRUCTED TO COMPLY WITH |
| | SECTION 11-4 (ACCESSIBLE ELEMENTS AND |
| | SPACES: SCOPE AND TECHNICAL REQUIREMENTS |
| | ALL BATHROOM SHALL BE ACCESSIBLE AND |
| | THE STAFF TOILET ROOM SHALL BE ACCESSI- |
| | BLE. PLEASE PROVIDE DETAILS. |
| | 2) SHT P6-2.01 DRINKING FOUNTAIN, SHOW |
| | COMPLIANCE WITH SEC 11-4.1.3(10)(A), |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY |
| | BEND OR STOOPING. |
| | 3) SEC. 11-4.13.9, DOOR HARDWARE. WHEN |
| | SLIDING DOORS ARE FULLY OPEN, OPERATING |
| | HARDWARE SHALL BE EXPOSED AND USABLE |
| | FROM BOTH SIDES. |
| | 4) SEC 11-4.13.11, DOOR OPENING FORCE. |
| | THE MAXIMUM FORCE FOR PUSHING OR PULLING |
| | OPEN A DOOR SHALL BE AS FOLLOWS PER |
| | (2)(C) SLIDING OR FOLDING DOORS: 5 LBF |
| | 5) SHT P6-3.01 DOMESTIC WATER RISER. |
| | WATER HAMMER ARRESTORS REQUIRED BY 406.9 |
| | FOR QUICK CLOSING VALVES, (WASH MACHINES |
| | DISHWASHERS, & ICE MAKERS), SHALL BE LO- |
| | CATED NEAR THE FIXTURES IN AN "EFFECTIVE |
| | RANGE" NOT AT THE TOP OF THE DROP. PER |
| | PDI-WH 201 AND MANUF. INSTALLATION IN- |
| | STRUCTIONS. |
| | 6) FOLLOWING COMMENTS FOR GAS PERMIT |
| | APPLICATION REQUIREMENTS. |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | GAS CODE. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 3) LISTED WATER HEATERS SHALL BE IN- |
| | STALLED IN ACCORDANCE WITH THEIR LISTING |
| | AND THE MANUFACTURES INTSRUCTIONS. THERE |
| | SHALL BE CLEARANCE FOR SERVICING HEATER. |
| | 4) SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 |
| | FUEL GAS CODE SEC 402.2. |
| | 5) SHTS P6-2.01 & P6-3.02 GAS PLAN VIEW |
| | & GAS RISER DIAGRAM, MANUAL SHUT OFF |
| | VALVE TO BE UPSTREAM OF SOLENOID VALVE, |
| | AND A UNION IS REQUIRED BETWEEN VALVES. |
| | |