Plan Review Notes
Plan Review Notes For Permit 02102207
Permit Number 02102207
Review Stop P
Sequence Number 1
Notes
Date Text
2002-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) PER SECTION 11-9.1.1, ALL PUBLIC USE
 AND COMMON USE AREAS ARE REQUIRED TO BE
 DESIGNED AND CONSTRUCTED TO COMPLY WITH
 SECTION 11-4 (ACCESSIBLE ELEMENTS AND
 SPACES: SCOPE AND TECHNICAL REQUIREMENTS
 ALL BATHROOM SHALL BE ACCESSIBLE AND
 THE STAFF TOILET ROOM SHALL BE ACCESSI-
 BLE. PLEASE PROVIDE DETAILS.
 2) SHT P6-2.01 DRINKING FOUNTAIN, SHOW
 COMPLIANCE WITH SEC 11-4.1.3(10)(A),
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BEND OR STOOPING.
 3) SEC. 11-4.13.9, DOOR HARDWARE. WHEN
 SLIDING DOORS ARE FULLY OPEN, OPERATING
 HARDWARE SHALL BE EXPOSED AND USABLE
 FROM BOTH SIDES.
 4) SEC 11-4.13.11, DOOR OPENING FORCE.
 THE MAXIMUM FORCE FOR PUSHING OR PULLING
 OPEN A DOOR SHALL BE AS FOLLOWS PER
 (2)(C) SLIDING OR FOLDING DOORS: 5 LBF
 5) SHT P6-3.01 DOMESTIC WATER RISER.
 WATER HAMMER ARRESTORS REQUIRED BY 406.9
 FOR QUICK CLOSING VALVES, (WASH MACHINES
 DISHWASHERS, & ICE MAKERS), SHALL BE LO-
 CATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT AT THE TOP OF THE DROP. PER
 PDI-WH 201 AND MANUF. INSTALLATION IN-
 STRUCTIONS.
 6) FOLLOWING COMMENTS FOR GAS PERMIT
 APPLICATION REQUIREMENTS.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3) LISTED WATER HEATERS SHALL BE IN-
 STALLED IN ACCORDANCE WITH THEIR LISTING
 AND THE MANUFACTURES INTSRUCTIONS. THERE
 SHALL BE CLEARANCE FOR SERVICING HEATER.
 4) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC 402.2.
 5) SHTS P6-2.01 & P6-3.02 GAS PLAN VIEW
 & GAS RISER DIAGRAM, MANUAL SHUT OFF
 VALVE TO BE UPSTREAM OF SOLENOID VALVE,
 AND A UNION IS REQUIRED BETWEEN VALVES.
  
 REVIEW BY KEN STEVENS