| Plan Review Notes For Permit 02102207 |
| Permit Number |
02102207 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-02 00:00:00 | 1ST PLAN CHECK | | | DENIED:REVIEW COTTAGES #6,7,10,9,10, | | | 11,12, & 13. | | | | | | GAS DRYERS ARE INDICATED ON THE PLUMBING | | | PLAN.PROVIDE CALCULATIONS INDICATING | | | WHETHER THEY ARE INSTALLED IN A | | | "CONFINED" OR "UNCONFINED" SPACE. | | | | | | PLEASE NOTE AS PER 2001 FBC(M) 504.5, | | | DRYER INSTALLATIONS EXHAUSTING MORE THAN | | | 200 CFMSHALL BE PROVIDED WITH MAKEUP | | | AIR. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL COMPLY WITH 2001 FBC(M) 606.4.1, | | | DETECTOR SHALL ACTIVATE A VISIBLE AND | | | AUDIBLE SUPERVISORY SIGNAL AT A | | | CONSTANTLY ATTENDED LOCATION OR SHALL | | | ACTIVATEA VISIBLE & AN AUDIBLE SIGNAL | | | IN AN APPROVED LOCATION IN NORMALLY | | | OCCUPIED AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|