Plan Review Notes
Plan Review Notes For Permit 02102207
Permit Number 02102207
Review Stop M
Sequence Number 1
Notes
Date Text
2002-12-02 00:00:001ST PLAN CHECK
 DENIED:REVIEW COTTAGES #6,7,10,9,10,
 11,12, & 13.
  
 GAS DRYERS ARE INDICATED ON THE PLUMBING
 PLAN.PROVIDE CALCULATIONS INDICATING
 WHETHER THEY ARE INSTALLED IN A
 "CONFINED" OR "UNCONFINED" SPACE.
  
 PLEASE NOTE AS PER 2001 FBC(M) 504.5,
 DRYER INSTALLATIONS EXHAUSTING MORE THAN
 200 CFMSHALL BE PROVIDED WITH MAKEUP
 AIR.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL COMPLY WITH 2001 FBC(M) 606.4.1,
 DETECTOR SHALL ACTIVATE A VISIBLE AND
 AUDIBLE SUPERVISORY SIGNAL AT A
 CONSTANTLY ATTENDED LOCATION OR SHALL
 ACTIVATEA VISIBLE & AN AUDIBLE SIGNAL
 IN AN APPROVED LOCATION IN NORMALLY
 OCCUPIED AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.