2003-01-10 00:00:001) HOW WILL THE COTTAGES BE LICENSED
 UNDER STATE, COUNTY, AND CITY
 REQUIREMENTS.
  
 2) PLEASE INDICATE THE AGES OF THE
 OCCUPANTS FOR THE COTTAGES AND
 APPROPRIATE STAFF RATIO'S.
  
 3) PLEASE PROVIDE A LIFE SAFETY PLAN
 INDICATING OCCUPANT LOADS AND TRAVEL
 DISTANCES TO EXITS.
  
 4) PLEASE INDICATE HOURS OF OPERATION
 FOR THE COTTAGES. WILL THE COTTAGES
 BE OPERATIONAL FULL TIME OR PART TIME.
  
 5) PLEASE PROVIDE A DATA BOX ON THE
 TITLE PAGE INDICATING APPROPRIATE CODES
 AND CONSTRUCTION TYPES FOR THE COTTAGES.
  
 6) IS THERE ANY COOKING PLANNED AT THE
 COTTAGES THAT WOULD CREATE SMOKE OR
 GREASE LADEN VAPORS.
  
 7) FIRE SPRINKLER HEADS APPEAR TO BE
 MISSING FROM THE MIDDLE OF SOCIAL ROOM.
  
 8) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF FIRE SPRINKLER
 SYSTEM.
  
 9) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE FIRE ALARM SYSTEMS.
  
 10) A KNOX-BOX ENTRY SYSTEM WILL BE
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910