| 2002-11-27 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE:PLEASE PROVIDE CIRCUITING ON | | | PLANS AND CORRELATE WITH SUBMITTED OANEL | | | SCHEDULES. | | | | | | 2)NOTE: PLEASE CLARIFY SD`S SHOWN IN | | | A/C CLOSET? ARE THESE DUCT DETECTORS? | | | | | | | | | 3)NOTE: PLEASE NOTE, ARC FAULT PROTECT- | | | -ION REQ`D FOR BEDROOM CIRCUITS. 210-12 | | | PLEASE SHOW ON PANEL SCHEDULES. | | | | | | 4)NOTE: PLEASE NOTE, REQ`D BATH CIRCUTIT | | | (S) MISSING. 210-52D/ PLEASE LIST ON | | | PANEL SCHEDULE PER 210-11-C-3 | | | | | | 5)NOTE: PLEASE CLARIFY MCB IN PANELS | | | STILL MEETING 230-76/230-79 FOR MANUAL | | | MEANS OF DISC AND RATED FOR THE LOAD | | | SERVED. PLEASE NOTE, A SHUNT TRIP IS | | | PERMITTED, HOWEVER, MCB STILL NEEDS TO | | | MEET THE ABOVE. | | | | | | 6)NOTE: PLEASE COMPLETE LOAD CALCUALTION | | | -S. | | | | | | PLEASE NOTE, THIS IS A TYPICAL REVIEW | | | FOR ALL COTTAGE UNITS, AS PLANS WERE | | | SUBMITTED FOR ALL AS TYPICAL. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|