Plan Review Notes
Plan Review Notes For Permit 02102207
Permit Number 02102207
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-27 00:00:00*************** UNSAT *****************
  
 1)NOTE:PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED OANEL
 SCHEDULES.
  
 2)NOTE: PLEASE CLARIFY SD`S SHOWN IN
 A/C CLOSET? ARE THESE DUCT DETECTORS?
  
  
 3)NOTE: PLEASE NOTE, ARC FAULT PROTECT-
 -ION REQ`D FOR BEDROOM CIRCUITS. 210-12
 PLEASE SHOW ON PANEL SCHEDULES.
  
 4)NOTE: PLEASE NOTE, REQ`D BATH CIRCUTIT
 (S) MISSING. 210-52D/ PLEASE LIST ON
 PANEL SCHEDULE PER 210-11-C-3
  
 5)NOTE: PLEASE CLARIFY MCB IN PANELS
 STILL MEETING 230-76/230-79 FOR MANUAL
 MEANS OF DISC AND RATED FOR THE LOAD
 SERVED. PLEASE NOTE, A SHUNT TRIP IS
 PERMITTED, HOWEVER, MCB STILL NEEDS TO
 MEET THE ABOVE.
  
 6)NOTE: PLEASE COMPLETE LOAD CALCUALTION
 -S.
  
 PLEASE NOTE, THIS IS A TYPICAL REVIEW
 FOR ALL COTTAGE UNITS, AS PLANS WERE
 SUBMITTED FOR ALL AS TYPICAL.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372