| Date |
Text |
| 2003-01-06 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC* 104.2.4A SIGNED AND SEALED |
| | SURVEY DRAWING IS REQUIRED. |
| | |
| | 2) FL. ADMIN. CODE 61G1-16.003EACH |
| | ARCHITECTURAL PLAN SHEET SHALL BE SIGNED |
| | PERSONALLY, NOT SIGNATURE STAMPED. |
| | |
| | 3) INFORMATIVE: |
| | A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 4) INFORMATIVE: |
| | IMPACT FEES SHALL BE PAID TO PALM BEACH |
| | COUNTY, THE PLANS STAMPED BY THEM AND A |
| | COPY OF THE RECEIPT SUBMITTED TO THE |
| | CITY OF WEST PALM BEACH CONSTRUCTION |
| | SERVICES DEPARTMET BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED. |
| | |
| | 5) FBC 11-4.1.2EACH OF THE BUILDINGS |
| | SHALL BE SERVED BY AT LEAST ONE |
| | ACCESSIBLE ROUTE FROM THE ACCESSIBLE |
| | PARKING.ACCEPTABILITY OF THESE PLANS |
| | IS CONTINGENT UPON UPON THE CIVIL/SITE |
| | PLANS, PERMIT# 02102208, BEING PERMITTED |
| | NOTE THAT THE SUBMITTED SITE PLAN (SHEET |
| | A7-1.1) DOES NOT SHOW A PATH TO THE |
| | ENTRANCE OF COTTAGE #7. |
| | |
| | 6) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR THE |
| | ROOFING, EXTERIOR DOORS AND WINDOWS. |
| | |
| | 8) FBC* 104.2NO FOUNDATIONS ARE SHOWN |
| | FOR THE COURTYARD ALUMINUM RAILING AND |
| | GATE.A SEPARATE PERMIT APPLICATION |
| | WILL BE REQUIRED. |
| | |
| | 9) FOUNDATION PLAN SHEET S-7.01 HAS |
| | 'MF-16' ANNOTATION AT THE MONOLITHIC |
| | FOOTING.THIS SHOULD BE 'WF-16' TO |
| | CORRELATE WITH THE FOOTING SCHEDULE. |
| | |
| | 10) FBC* TABLE 2306.1STRUCTURAL NOTES, |
| | SHEET STR-GN, PLYWOOD ROOF DECKING.THE |
| | PERIMETER ZONE AT THE GABLE ENDS SHALL |
| | HAVE NAILS SPACED AT 4"O.C. MAXIMUM, TO |
| | A DISTANCE OF 5 FEET (NOT 24") FROM THE |
| | EDGE OF THE ROOF. |
| | |
| | 11) STRUCTURAL NOTES, SHEET STR-GN, WOOD |
| | TRUSS NOTE 6.IT IS NOTED THAT THE |
| | TRUSS DESIGN ENGINEER IS TO PROVIDE THE |
| | WIND UPLIFT REACTIONS.THE PERMIT |
| | CANNOT BE ISSUED UNTIL THE REACTIONS ARE |
| | SPECIFIED ON THE PLANS FOR CROSS |
| | REFERENCE AGAINST THE PROPOSED TRUSS |
| | ANCHORS AND STRAPS. |
| | |
| | 12) FBC 410.2.2 FIRE SEPARATION.THE |
| | LAUNDRY ROOM SHALL BE SEPARATED FROM |
| | OTHER ROOMS BY 1-HOUR RATED WALLS AND |
| | 3/4-HOUR DOORS.SHEET A7-2.1 SHOWS |
| | PARTITION TYPES C AND I WHICH ARE NON- |
| | RATED. |
| | |
| | 13) FBC 2309.6ATTIC ACCESS.THE ATTIC |
| | ACCESS PANELS SHOWN ON SHEET A7-11.1 ARE |
| | NOT DIMENSIONED.ATTIC ACCESS OPENINGS |
| | SHALL BE NOT LESS THAN 20X36 INCHES. |
| | |
| | 14) FBC 2405.2THE GLAZED PANEL |
| | ADJACENT TO THE STAFF OFFICE DOOR IS |
| | MARKED AS REF *H.NO DETAILS ARE GIVEN |
| | IN THE SCHEDULE ON SHEET A7-10.1, WHICH |
| | ONLY GOES UP TO REF F.THE GLAZED PANEL |
| | IS IN A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).SUBMIT DETAILS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 15) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |