2003-01-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4A SIGNED AND SEALED
 SURVEY DRAWING IS REQUIRED.
  
 2) FL. ADMIN. CODE 61G1-16.003EACH
 ARCHITECTURAL PLAN SHEET SHALL BE SIGNED
 PERSONALLY, NOT SIGNATURE STAMPED.
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES SHALL BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMET BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2EACH OF THE BUILDINGS
 SHALL BE SERVED BY AT LEAST ONE
 ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING.ACCEPTABILITY OF THESE PLANS
 IS CONTINGENT UPON UPON THE CIVIL/SITE
 PLANS, PERMIT# 02102208, BEING PERMITTED
 NOTE THAT THE SUBMITTED SITE PLAN (SHEET
 A7-1.1) DOES NOT SHOW A PATH TO THE
 ENTRANCE OF COTTAGE #7.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING, EXTERIOR DOORS AND WINDOWS.
  
 8) FBC* 104.2NO FOUNDATIONS ARE SHOWN
 FOR THE COURTYARD ALUMINUM RAILING AND
 GATE.A SEPARATE PERMIT APPLICATION
 WILL BE REQUIRED.
  
 9) FOUNDATION PLAN SHEET S-7.01 HAS
 'MF-16' ANNOTATION AT THE MONOLITHIC
 FOOTING.THIS SHOULD BE 'WF-16' TO
 CORRELATE WITH THE FOOTING SCHEDULE.
  
 10) FBC* TABLE 2306.1STRUCTURAL NOTES,
 SHEET STR-GN, PLYWOOD ROOF DECKING.THE
 PERIMETER ZONE AT THE GABLE ENDS SHALL
 HAVE NAILS SPACED AT 4"O.C. MAXIMUM, TO
 A DISTANCE OF 5 FEET (NOT 24") FROM THE
 EDGE OF THE ROOF.
  
 11) STRUCTURAL NOTES, SHEET STR-GN, WOOD
 TRUSS NOTE 6.IT IS NOTED THAT THE
 TRUSS DESIGN ENGINEER IS TO PROVIDE THE
 WIND UPLIFT REACTIONS.THE PERMIT
 CANNOT BE ISSUED UNTIL THE REACTIONS ARE
 SPECIFIED ON THE PLANS FOR CROSS
 REFERENCE AGAINST THE PROPOSED TRUSS
 ANCHORS AND STRAPS.
  
 12) FBC 410.2.2 FIRE SEPARATION.THE
 LAUNDRY ROOM SHALL BE SEPARATED FROM
 OTHER ROOMS BY 1-HOUR RATED WALLS AND
 3/4-HOUR DOORS.SHEET A7-2.1 SHOWS
 PARTITION TYPES C AND I WHICH ARE NON-
 RATED.
  
 13) FBC 2309.6ATTIC ACCESS.THE ATTIC
 ACCESS PANELS SHOWN ON SHEET A7-11.1 ARE
 NOT DIMENSIONED.ATTIC ACCESS OPENINGS
 SHALL BE NOT LESS THAN 20X36 INCHES.
  
 14) FBC 2405.2THE GLAZED PANEL
 ADJACENT TO THE STAFF OFFICE DOOR IS
 MARKED AS REF *H.NO DETAILS ARE GIVEN
 IN THE SCHEDULE ON SHEET A7-10.1, WHICH
 ONLY GOES UP TO REF F.THE GLAZED PANEL
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499