Date Text
2005-11-15 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE SEE REVIEW DATED 7/18/05
 WITH RESPECT TO GENERATOR INSTALLATION.
 NO PERMIT APPLICATION TO DATE HAS BEEN
 MADE FOR NEW GENERATOR. THIS MAY NOT BE
 INCLUDED UNDER BASE BLDG.
 PLEASE ALSO KNOW, A REVIEW FOR CODE
 COMPOLIANCE WILL BE DONE AT THAT TIME.
 PLEASE BE SURE TO SEE 2002 NEC,
 225.31-225.39, 445, 700ETC FOR
 REQUIREMENTS.
  
 2)NOTE: PLEASE SEE ALL ELECTRICAL SHEETS
 SHALL CLEARLY SHOW REVISIONS, DATES,
 IDENTIFIED BY CLOUDS AND TRIANGLES.
 PLEASE KNOW: A RESPONSE LETTER TELLING
 OF REV'S MADE ANDSCOPE OF WORK WILL HELP
 GREATLY IN EXPEDITING THE PLAN REVIEW
 PROCESS.
  
  
 ** PLEASE SEE COMMENTS #1, PLEASE DO NOT
 SUBMIT REVISION FOR THIS UNTIL GENERATOR
 PERMIT HAS BEEN ISSUED.
 PLEASE BE SURE WHEN THAT DOES OCCUR THAT
 PLANS REFERENCE GENERATORUNDER
 SEPARATE PERMIT,,#( ? ).
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]