Plan Review Notes
Plan Review Notes For Permit 02102206
Permit Number 02102206
Review Stop E
Sequence Number 7
Notes
Date Text
2005-07-18 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS ARE NOW COMING
 IN WITH A NEW GENERATOR SYSTEM WHICH WAS
 NO PART OF ORIGIANL PLANS. PLEASE SEE
 GEN SHALL BE UNDER A SEPARATE PERMIT.
 PLEASE SUBMIT COMPLETE PACKAGE FOR GEN
 REVIEW.
 PLEASE BE SURE TO SEE 2002 FOR ALL GEN
 REQUIREMENTS.
 450.13,702.5, ETC
 PLEASE SUBMIT ALL SPECS/MANUFACTURE
 SHEETS FOR GEN, ATS, ANY SUB0BASE FUEL
 TANK ?
 GEN'S SHALL BE SIZED FOR LOADS TO BE
 SERVED.
  
 SUBMIT REVISED PLANS WHEN GEN AND ALL
 TRADES RELATING TO GEN HAVE BEEN APPLIED
 FOR AND ISSUED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEYPALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-15 00:00:00IN ELECTRIC FOR REVIEW.