| 2005-08-17 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | REVISION SUBMITTED ON 7/6/05 FOR NEW |
| | DESIGN FOR THE EDUCATION BUILDING. |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FBC TABLE 704.2.4(FOOT NOTE 2) EXIT |
| | ACCESS CORRIDORS IN EDUCATIONAL |
| | OCCUPANCY.SHEET A5-2.1 THE INSTRUCTION |
| | ROOMS DO NOT HAVE AT LEAST ONE EXIT DOOR |
| | DIRECTLY TO THE OUTSIDE SO THE EXIT |
| | ACCESS CORRIDOR (102) IS REQUIRED TO BE |
| | ONE-HOUR FIRE-RATED.ALSO, THE ROOM |
| | DOORS LEADING TO THE CORRIDOR ARE |
| | REQUIRED TO BE 20-MINUTE FIRE-RATED. |
| | AMEND THE PLANS AND DOOR SCHEDULE. |
| | |
| | 2) FBC 11-4.16.4WATER CLOSET GRAB BARS |
| | SHEET A5-4.1.INTERIOR ELEVATIONS 3B, |
| | 4B, 5B AND 6B SHOW THE LENGTH OF THE |
| | SIDE GRAB BAR AS 3'-0".THIS SHOULD BE |
| | 3'-6".AMEND THE PLANS. |
| | |
| | 3) FBC 1606.1.3UPLIFT AT HIP TRUSSES. |
| | SHEET S-5.02 THE FOUR HIP TRUSSES ARE |
| | MARKED WITH THE SAME TYPE 1 'TRUSS TO |
| | WALL CONNECTION' THAT IS USED FOR THE |
| | TYPICAL TRUSS.THE TRIBUTARY AREA FOR |
| | THE HIP TRUSSES EXCEEDS THAT OF THE |
| | TYPICAL TRUSS AND AND RESULTS IN AN |
| | UPLIFT THAT EXCEEDS THE CAPACITY OF THE |
| | PROPOSED USP HTA12 TRUSS ANCHOR.AMEND |
| | THE PLAN OR SUBMIT CALCULATIONS TO |
| | JUSTIFY THE PROPOSED TRUSS ANCHOR FOR |
| | THIS APPLICATION. |
| | |
| | 4) FBC* 104.2 SHEET S-5.03, SECTION G. |
| | THE PROPOSED USE OF 'THREADED ROD WITH |
| | 4" EMBEDMENT' TO ATTACH THE 3X6'S @ 16" |
| | O.C. TO THE 3X10 AND TO THE 3X6 LEDGER |
| | IS NOT A RECOGNISED WOOD-TO-WOOD |
| | CONNECTION DETAIL.AMEND/CLARIFY THIS |
| | DETAIL. |
| | |
| | 5) SHEET A5-10.1, DOOR SCHEDULE.DOOR |
| | 113A IS SHOWN AS BEING 5 FEET WIDE. |
| | SHEET A5-2.1 DOES NOT INDICATE A 5 FOOT |
| | WIDE DOOR.AMEND/CLARIFY THE PLANS. |
| | |
| | 6) SUBMIT PRODUCT APPROVALS FOR THE |
| | GLASS BLOCK WINDOWS, THE SECTIONAL |
| | OVERHEAD DOORS (DOORS 117B AND 118B)AND |
| | THELOUVER DOORS (DOORS 105A, 106A AND |
| | 116A). |
| | |
| | 7) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS, TO FORM A SET OF |
| | 'OLD/VOID SHEETS', FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |