2005-08-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 7/6/05 FOR NEW
 DESIGN FOR THE EDUCATION BUILDING.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC TABLE 704.2.4(FOOT NOTE 2) EXIT
 ACCESS CORRIDORS IN EDUCATIONAL
 OCCUPANCY.SHEET A5-2.1 THE INSTRUCTION
 ROOMS DO NOT HAVE AT LEAST ONE EXIT DOOR
 DIRECTLY TO THE OUTSIDE SO THE EXIT
 ACCESS CORRIDOR (102) IS REQUIRED TO BE
 ONE-HOUR FIRE-RATED.ALSO, THE ROOM
 DOORS LEADING TO THE CORRIDOR ARE
 REQUIRED TO BE 20-MINUTE FIRE-RATED.
 AMEND THE PLANS AND DOOR SCHEDULE.
  
 2) FBC 11-4.16.4WATER CLOSET GRAB BARS
 SHEET A5-4.1.INTERIOR ELEVATIONS 3B,
 4B, 5B AND 6B SHOW THE LENGTH OF THE
 SIDE GRAB BAR AS 3'-0".THIS SHOULD BE
 3'-6".AMEND THE PLANS.
  
 3) FBC 1606.1.3UPLIFT AT HIP TRUSSES.
 SHEET S-5.02 THE FOUR HIP TRUSSES ARE
 MARKED WITH THE SAME TYPE 1 'TRUSS TO
 WALL CONNECTION' THAT IS USED FOR THE
 TYPICAL TRUSS.THE TRIBUTARY AREA FOR
 THE HIP TRUSSES EXCEEDS THAT OF THE
 TYPICAL TRUSS AND AND RESULTS IN AN
 UPLIFT THAT EXCEEDS THE CAPACITY OF THE
 PROPOSED USP HTA12 TRUSS ANCHOR.AMEND
 THE PLAN OR SUBMIT CALCULATIONS TO
 JUSTIFY THE PROPOSED TRUSS ANCHOR FOR
 THIS APPLICATION.
  
 4) FBC* 104.2 SHEET S-5.03, SECTION G.
 THE PROPOSED USE OF 'THREADED ROD WITH
 4" EMBEDMENT' TO ATTACH THE 3X6'S @ 16"
 O.C. TO THE 3X10 AND TO THE 3X6 LEDGER
 IS NOT A RECOGNISED WOOD-TO-WOOD
 CONNECTION DETAIL.AMEND/CLARIFY THIS
 DETAIL.
  
 5) SHEET A5-10.1, DOOR SCHEDULE.DOOR
 113A IS SHOWN AS BEING 5 FEET WIDE.
 SHEET A5-2.1 DOES NOT INDICATE A 5 FOOT
 WIDE DOOR.AMEND/CLARIFY THE PLANS.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE
 GLASS BLOCK WINDOWS, THE SECTIONAL
 OVERHEAD DOORS (DOORS 117B AND 118B)AND
 THELOUVER DOORS (DOORS 105A, 106A AND
 116A).
  
 7) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN