| Notes |
| Date |
Text |
| 2005-10-09 00:00:00 | PAUL SCHMITZ | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE | | | PLAN REVIEW, DENIED | | | WHEN RE- SUBMITTING PLANS PLEASE SUBMITT | | | A TRANSMITTAL LETTER FOR ALL DISCIPLINES | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE. IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 1) PLEASE ADDRESS PREVIOUS COMMENTS, | | | DATED 8-05-05 BY KEN STEVENS | | | | | | 2. SHTS P5-2.01 & 5-3.01 THE BACKFLOW | | | FOR THE 1/2" WATER LINE TO AHU-3 SHALL | | | BE LOCATED A MAXIMUM OF 4' ABOVE FINISH | | | FLOOR FOR SERVICE AND CERTIFICATION. | | | SHT M5-601,NOTE #4 MOUNT AHU BELOW | | | CEILING, PLEASE CLARIFY. | | | 3. AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE OF THE BUILDING. SECTION | | | 608.13.2. | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | | | | | | | | | | | |
|