Plan Review Notes
Plan Review Notes For Permit 02102206
Permit Number 02102206
Review Stop P
Sequence Number 5
Notes
Date Text
2005-10-09 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE
 PLAN REVIEW, DENIED
 WHEN RE- SUBMITTING PLANS PLEASE SUBMITT
 A TRANSMITTAL LETTER FOR ALL DISCIPLINES
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE. IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PLEASE ADDRESS PREVIOUS COMMENTS,
 DATED 8-05-05 BY KEN STEVENS
  
 2. SHTS P5-2.01 & 5-3.01 THE BACKFLOW
 FOR THE 1/2" WATER LINE TO AHU-3 SHALL
 BE LOCATED A MAXIMUM OF 4' ABOVE FINISH
 FLOOR FOR SERVICE AND CERTIFICATION.
 SHT M5-601,NOTE #4 MOUNT AHU BELOW
 CEILING, PLEASE CLARIFY.
 3. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE BUILDING. SECTION
 608.13.2.
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  