| Plan Review Notes For Permit 02102206 |
| Permit Number |
02102206 |
|
| Review Stop |
FIRE |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-11-17 00:00:00 | ******DENIED****** | | | REVISION DATED 9/9/05 | | | PLANS APPROVED ON 4/24/03 | | | | | | 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS | | | REGARDING THE GENERATOR. | | | | | | 2) DRAWINGS SHOW (2) DRY FIRE SPRINKLER | | | HEADS AND NO COVERAGE IN TEL. COMM. | | | ROOM. PLEASE EXPLAIN, AS THIS | | | ARRANGEMENT WOULD NOT BE ACCEPTABLE. | | | | | | 3) AS A REMINDER, SEPARATE SHOP DRAWINGS | | | FOR FIRE SPRINKLER AND FIRE ALARM | | | SYSTEMS ARE REQUIRED. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/ WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|