| Plan Review Notes For Permit 02102206 |
| Permit Number |
02102206 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-08-05 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | A. THIS REVISION IS A COMPLETE CHANGE OF | | | THE FLOOR PLAN. | | | 1. SHT A5-4.1 DETAIL #2 WATER CLOSETS | | | SHALL BE 1'6" FROM THE SIDE WALL TO THE | | | CENTERLINE OF THE FIXTURE. 1'8" SHOWN. | | | FIGURE 28. | | | 2. SHTS P5-2.01 & 5-3.01 THE BACKFLOW | | | FOR THE 1/2" WATER LINE TO AHU-3 SHALL | | | BE LOCATED A MAXIMUM OF 4' ABOVE THE | | | FLOOR FOR SERVICE AND CERTIFICATION. - | | | NO CONDENSATE IS SHOWN FOR AHU-3. PLEASE | | | CLARIFY IF THERE WILL BE A CONDENSATE | | | LINE FOR THE AIR HANDLER. | | | 3. AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE OF THE BUILDING. SECTION | | | 608.13.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|