2005-08-05 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A. THIS REVISION IS A COMPLETE CHANGE OF
 THE FLOOR PLAN.
 1. SHT A5-4.1 DETAIL #2 WATER CLOSETS
 SHALL BE 1'6" FROM THE SIDE WALL TO THE
 CENTERLINE OF THE FIXTURE. 1'8" SHOWN.
 FIGURE 28.
 2. SHTS P5-2.01 & 5-3.01 THE BACKFLOW
 FOR THE 1/2" WATER LINE TO AHU-3 SHALL
 BE LOCATED A MAXIMUM OF 4' ABOVE THE
 FLOOR FOR SERVICE AND CERTIFICATION. -
 NO CONDENSATE IS SHOWN FOR AHU-3. PLEASE
 CLARIFY IF THERE WILL BE A CONDENSATE
 LINE FOR THE AIR HANDLER.
 3. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE BUILDING. SECTION
 608.13.2.
  