| 2003-06-05 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 1/10/03 AND 4/18/03: |
| | |
| | 1) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC* 104.2.4SITE SURVEY.A SIGNED AND |
| | SEALED SURVEY DRAWING PREPARED BY A |
| | QUALIFIED SURVEYOR IS REQUIRED (REF: |
| | 472.025(1) FL. STATUTES.). THE SUBMITTED |
| | SURVEY SHEET IS FOR A DELRAY BEACH |
| | LOCATION (???) |
| | |
| | 3) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 4) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, THE PLANS STAMPED BY THEM |
| | AND A COPY OF THE RECEIPT SUBMITTED TO |
| | THE CITY OF WEST PALM BEACH CONSTRUCTION |
| | SERVICES DEPARTMENT BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED. |
| | |
| | 5) FBC 11-4.1.2THE BUILDING SHALL BE |
| | SERVED BY AT LEAST ONE ACCESSIBLE ROUTE |
| | FROM THE ACCESSIBLE PARKING AND THE BUS |
| | STOP.ACCEPTABILITY OF THIS PERMIT |
| | APPLICATION IS CONTINGENT UPON THE |
| | CIVIL/SITE PLANS, UNDER PERMIT 02102208, |
| | BEING PERMITTED. |
| | |
| | 6) FBC 13-103.1.1.1 AND 103.1.2SHEET 2 |
| | OF THE SUBMITTED ENERGY CODE COMPLIANCE |
| | FORMS SHALL BE SIGNED BY THE OWNER (OR |
| | THE PROJECT ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT DESIGNATED BY THE |
| | OWNER) TO CERTIFY COMPLIANCE WITH THE |
| | CODE.ALSO, THE ARCHITECT'S NAME AND |
| | REGISTRATION NUMBER SHALL BE ADDED ABOVE |
| | THOSE OF THE OTHER SYSTEM DESIGNERS.ON |
| | SHEET 1, COMPLETE THE PROJECT DETAILS |
| | INCLUDING NAME OF OWNER, PROJECT ADDRESS |
| | (4888 N. HAVERHILL RD), ZIP (33417) |
| | AND PERMIT NUMBER (02102206). |
| | |
| | 7) PRODUCT APPROVALS.THE PRODUCT |
| | APPROVAL SHEETS SHALL BE MARKED, AS |
| | APPROPRIATE TO IDENTIFY WHICH PRODUCT |
| | OPTIONS/MATERIALS ARE TO BE USED, ALSO: |
| | (A) THE SUBMITTED COPIES OF TIMBERLINE |
| | SELECT 40 ASPHALT SHINGLE PRODUCT |
| | APPROVAL NOA# 03-0219.08 IS MISSING |
| | SHEET 3 OF 3.ALSO, SHEET 2 IS A POOR |
| | COPY.SUBMIT TWO COPIES OF A COMPLETE |
| | AND LEGIBLE PRODUCT APPROVAL. |
| | (G) THE DRAWING SHEETS OF THE SUBMITTED |
| | COPIES OF ARCH ALUMINUM NARROW STILE |
| | DOOR PRODUCT APPROVAL NOA# 01-0910.09 |
| | ARE POORLY REPRODUCED.SUBMIT LEGIBLE |
| | COPIES.NOTE THAT THESE DOORS ARE NOT |
| | IMPACT RESISTANT, AND WILL REQUIRE THE |
| | INSTALLATION OF HURRICANE SHUTTERS. |
| | COPIES OF MIAMI-DADE PRODUCT APPROVALS |
| | CAN BE PRINTED FROM THEIR WEBSITE,WWW. |
| | MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM |
| | (H) THE SUBMITTED ARCH ALUMINUM SERIES |
| | 4500 STOREFRONT PRODUCT APPROVAL NOA# |
| | 00-1220.05 IS FOR A NON-IMPACT RATED |
| | SYSTEM.THE INSTALLATION OF HURRICANE |
| | MISSILE IMPACT PROTECTION SHUTTERS WILL |
| | BE REQUIRED.THE PLANS SHALL IDENTIFY |
| | WHERE THIS SYSTEM IS TO BE USED AND A |
| | HURRICANE MISSILE IMPACT PROTECTION |
| | SHUTTER PRODUCT APPROVAL SHALL BE |
| | SUBMITTED. |
| | |
| | 13) NOTED: |
| | SHEET A5-1.1, BUILDING CODE ANALYSIS |
| | TABLE, STATES MINIMUM ALLOWABLE |
| | CONSTRUCTION TYPE VI. |
| | |
| | 15) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | END OF REVIEW COMMENTS |