2003-04-24 00:00:00PROVISO:
  
 PLAN SHEET M5-2.01 STAFF TOILET ROOM
 #122, INDICATES A RETURN AIR GRILLE IN
 THE TOILET ROOM.AS PER 2001 FBC(M)
 TABLE 403.3 NOTE B, MECHANICAL EXHAUST
 REQUIRED & RECIRCULATION IS PROHIBITED
 FROM PUBLIC RESTROOMS. PLEASE RELOCATE
 RETURN AIR GRILLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.