| 2003-04-17 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 1/10/03: |
| | |
| | 1) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC* 104.2.4A SIGNED AND SEALED SURVEY |
| | DRAWING IS REQUIRED.THE SUBMITTED |
| | SURVEY SHEET IS FOR A DELRAY BEACH |
| | LOCATION (???) |
| | |
| | 3) INFORMATIVE: |
| | A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 4) INFORMATIVE: |
| | IMPACT FEES MUST BE PAID TO PALM BEACH |
| | COUNTY, THE PLANS STAMPED BY THEM AND A |
| | COPY OF THE RECEIPT SUBMITTED TO THE |
| | CITY OF WEST PALM BEACH CONSTRUCTION |
| | SERVICES DEPARTMENT BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED. |
| | |
| | 5) FBC 11-4.1.2THE BUILDING SHALL BE |
| | SERVED BY AT LEAST ONE ACCESSIBLE ROUTE |
| | FROM THE ACCESSIBLE PARKING AND BUS STOP |
| | ACCEPTABILITY OF THESE PLANS IS |
| | CONTINGENT UPON THE CIVIL/SITE PLANS, |
| | PERMIT# 02102208, BEING PERMITTED. |
| | |
| | 6) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 7) PRODUCT APPROVALS: DOOR, WINDOW, ROOF |
| | (A) ASPHALT SHINGLE PRODUCT APPROVAL |
| | NOA# 00-0105.02 WILL EXPIRE ON 4/22/03. |
| | IF THIS OCCURS BEFORE THE A PERMIT |
| | APPLICATION IS MADE, THEN THE PRODUCT |
| | APPROVAL IS NOT VALID AND NEW ONE SHALL |
| | BE SUBMITTED. |
| | (B) THE SUBMITTED COPY OF STEELCRAFT |
| | MANUF. 98/99 RIM EXIT STEEL DOOR PRODUCT |
| | APPROVAL NOA# 01-1203.11 IS MISSING TEXT |
| | SHEETS 2 AND 3 (SPECIFIC AND GENERAL |
| | CONDITIONS), AND SOME OF THE DRAWING |
| | SEETS.SUBMIT A COMPLETE PRODUCT |
| | APPROVAL. |
| | (C) THE SUBMITTED COPY OF STEELCRAFT |
| | MANUF. F,M FRAME STEEL DOOR PRODUCT |
| | APPROVAL NOA# 01-0129.12 IS MISSING TEXT |
| | SHEETS 2 AND 3 (SPECIFIC AND GENERAL |
| | CONDITIONS), AND SOME OF THE DRAWING |
| | SHEETS.SUBMIT A COMPLETE PRODUCT |
| | APPROVAL. |
| | (D) SHEET A5-10.1, WNDOW SCHEDULE. |
| | THE WIDTH OF WINDOW TYPE B, AT 7 FEET, |
| | IS OUTSIDE THE SCOPE OF THE SUBMITTED |
| | ARCH ALUMINUM WINDOW WALL PRODUCT |
| | APPROVAL NOA# 01-0329.02 AND THE |
| | SUBMITTED PGT INDUSTRIES FIXED WINDOW |
| | PRODUCT APPROVAL NOA# 02-0716.03. SUBMIT |
| | A PRODUCT APPROVAL WHICH COVERS THE |
| | SPECIFIED WINDOW DIMENSIONS. |
| | (E) THE DRAWING SHEETS OF THE SUBMITTED |
| | COPIES OF ARCH ALUMINUM STOREFRONT DOOR |
| | PRODUCT APPR. NOA# 01-0919.02 ARE POORLY |
| | REPRODUCED. SUBMIT LEGIBLE COPIES. |
| | COPIES OF MIAMI-DADE PRODUCT APPROVALS |
| | CAN BE PRINTED FROM THEIR WEBSITE,WWW. |
| | MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM |
| | (F) THE SUBMITTED 2 PAGE COPY EXTRACT OF |
| | THE 48 PAGE GAF MODIFIED BITUMEN ROOF |
| | PRODUCT APPROVAL NOA# 00-0331.09 DOES |
| | NOT INCLUDE A STATEMENT OF THE MAXIMUM |
| | DESIGN PRESSURE AND STATES THAT "ALL |
| | GENERAL AND SYSTEM LIMITATIONS SHALL |
| | APPLY".SUBMIT COPIES OF THE SHEETS |
| | WHICH STATE THE GENERAL AND SYSTEM |
| | LIMITATIONS AND THE MAX DESIGN PRESSURE. |
| | COPIES OF MIAMI-DADE PRODUCT APPROVALS |
| | CAN BE PRINTED FROM THEIR WEBSITE,WWW. |
| | MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM |
| | |
| | 8) FBC* TABLE 2306.1STRUCTURAL NOTES, |
| | SHEET STR-GN, PLYWOOD ROOF DECKING |
| | NOTE 3B.THE REVISION MADE, PER THE |
| | G.D. KLIEGER COMMENT RESPONSE LETTER, IS |
| | NOTED.THE * FOLLOWING THE REFERENCE TO |
| | FBC MEANS CITY OF WPB AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE (SEE KEY ABOVE). |
| | THE AMENDED TABLE REQUIRES THE PERIMETER |
| | ZONE AT THE GABLE END TO HAVE NAILS |
| | SPACED AT 4"O.C. MAXIMUM, FOR A DISTANCE |
| | OF 5 FT (NOT 4 FT) FROM THE EDGE OF THE |
| | ROOF. |
| | |
| | 9) SHEET S-5.02, ROOF TRUSS ANCHORS. |
| | THE ADDITION OF TYPICAL TRUSS ANCHOR |
| | SPECIFICATION, PER THE K.D. KLIEGER |
| | COMMENT RESPONSE LETTER OF 2/5/03, IS |
| | NOTED.THE PLAN SHALL STILL BE AMENDED |
| | TO STATE THE WORST CASE UPLIFT TO BE |
| | RESISTED BY THESE ANCHORS.NOTE THE |
| | IMPLICATIONS OF COMMENT 14 BELOW. |
| | |
| | 13) SHEET A5-1.1, BUILDING CODE ANALYSIS |
| | TABLE.THE STATED CONSTRUCTION TYPE HAS |
| | REVISED FROM TYPE V TO TYPE VI.THIS IS |
| | NOT CONSISTENT WITH THE CONSTRUCTION |
| | SHOWN ON SHEETS S-5.O1, S-5.03 AND |
| | A5-6.1 THRO' A5-7.2.AMEND SHEET AS |
| | REQUIRED. |
| | |
| | 14) COLD FORM METAL TRUSSES.SHEETS |
| | A5-2.2, A5-5.1 THRO' A5-7.2 HAVE ALL |
| | BEEN REVISED TO SHOW COLD FORM METAL |
| | TRUSSES.THE REVISION DOES NOT |
| | CORRELATE WITH SHEETS S-5.02, S-5.03 OR |
| | STR-GN WHICH ALL STILL REFER TO WOOD |
| | TRUSSES.AMEND THE PLANS. |
| | |
| | 15) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |