2006-08-16 00:00:00REVISED BLDG PLANS, GEN IS UNDER
 06050208
  
 REDLING MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM GEN TO BLDG.
 250.122 #3 MIN AS SHOWN UNDER GEN
 PERMIT.