Plan Review Notes
Plan Review Notes For Permit 02102206
Permit Number 02102206
Review Stop B
Sequence Number 11
Notes
Date Text
2006-06-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 4/24/06
  
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1004.1.2 AND 1004.1.4 EXCEPTION 2
 SHEET A5-2.1, MEETING SPACE (RM 113/115)
 FORMED BY UNITING ROOMS 113 AND 115 NOW
 HAS AN OCCUPANCY OF 65 PERSONS.EVERY
 ROOM WITH AN OCCUPANCY OF 50 OR MORE
 PERSONS SHALL HAVE NOT LESS THAN TWO
 EXIT ACCESS DOORS.AS THIS IS A
 SPRINKLERED BUILDING, THE EXIT ACCESS
 DOORS MUST BE AT A DISTANCE APART NOT
 LESS THAN 1/3 THE MAXIMUM DIAGONAL
 DIMENSION OF THE ROOM (THE REQUIRED
 SEPARATION WOULD BE 1/2 THE DIAGONAL IF
 THE BUILDING WERE NOT SPRINKLERED).
 RELOCATE DOOR 113.A AND/OR 115.A TO
 COMPLY.PLEASE NOTE THAT DOOR 109.B IS
 NOT CONSIDERED AS AN EXIT ACCESS DOOR.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]