2006-09-11 00:00:00PROVISO FROM REVIEW DATED 6/20/06:
  
 REVISION TO PLAN SHEET M5-2.01 INDICATES
 REMOVING AHU-3 FROM THE TEL/COMM ROOM
 #118.PLEASE CLARIFY THE RATING OF THIS
 WALL PENETRATION.DOES THE RATING GO
 BEYOND THE DROP RATED CEILING OR END AT
 THE CEILING?PLEASE REVISE THE WALL
 DETAIL SHOULD THE RATING STOP AT THE
 CEILING.
  
  
 NEW PROVISO:
 GENERAL NOTES: REVISION ADDED NOTE #4
 WHICH INDICATES THE HVAC CLOSET WILL NOW
 SERVE AS A PLENUM AND ALL DEVICES
 LOCATED IN THE SPACE SHALL BE PLENUM
 RATED.PLEASE NOTE, THIS SHALL INCLUDE
 THE DOOR AND DOOR FRAME.
  