| 2006-05-14 00:00:00 | *******UNSAT ********* |
| | |
| | 1) NOTE: PLEASE SEE NOTES DATED ON ALL |
| | PREVIOUS REVIEWS AND NOTES DATED |
| | 7/18/05, 11/15/05,12/20/05. |
| | GEN, ATSIS NOTE PART OF PERMIT. |
| | PLANS , PERMIT APPLICATION AND FEES |
| | SHALL BE SUBMITTED BEFORE ANY ANY OTHER |
| | ELECTRICAL REVISIONS ARE DONE. |
| | PLEASE KNOW, THE ELECTRICAL RISER AS |
| | SHOWN DOES NOT MEET CODE COMPLIANCE AND |
| | PREVIOUS PLANS WERE REDLINED NOT TO |
| | INCLUDE ATS AND GEN. |
| | PLEASE SUBMIT ALL INFORMATION FOR |
| | GENERATOR PERMIT. |
| | PLEASE SEE 225.31-225.39, 702.5, SUBMIT |
| | COMPLETE PACKAGE. |
| | PLEASE INCLUDE ALL SPECS/MANUAFCTURES |
| | CUT SHEETS FOR GEN, ATS, AND FUEL SUPPLY |
| | TANKS IF DIESEL/ PROPANE ETC. |
| | ** PLEASE KNOW, A ROUGH INSPECTION WILL |
| | NOT BE GIVEN AND THE PERMIT FOR |
| | ELECTRICAL MAY BE REVOKED AS NOTES HAVE |
| | NOT BEEN COMPLIED WITH FOR ALMOST 1 |
| | YEAR.(10 MONTHS) |
| | |
| | PLEASE KNOW, ONCE PERMIT FOR GEN IS |
| | ISSUED, OTHER REVISIONS CAN BE REVIEWED |
| | AT THAT TIME. |
| | |
| | 2) NOTE: PLEASE SEE ADDRESS ON PLANS IS |
| | NOT CORRECT. PLEASE SEE ADDRESS GIVEN |
| | FOR PERMITTING OF THIS BUILDING WAS |
| | "4888", PLANS READ 4884 WHICH IS THE |
| | SITE ADDRESS. |
| | TITLE BLOCKS FOR ALL SHEETS SHALL BE |
| | REVISED. FAC 61G1-16.004,61G15-23.002. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |