| Plan Review Notes For Permit 02102206 |
| Permit Number |
02102206 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT 5-2.1 MINIMUM FACILITIES REQUIRE | | | 2 DRINKING FOUNTAINS. A HI/LOW DRINKING | | | FOUNTAIN IS CONSIDERED 1 FIXTURE SO ONE | | | MORE DRINKING FOUNTAIN IS REQUIED. TABLE | | | 403.1 | | | 2) SHTS A5-2.1 & A5-4.1, TOILET ROOMS | | | #144 & 122, IF TOILET FACILITIES ARE | | | PROVIDED ON A SITE, THEN EACH SUCH PUB- | | | LIC AND COMMON USE TOILET FACILITY SHALL | | | COMPLY WITH 11-4.22 PER SECTION 11-4.1.2 | | | (6). | | | 3) SHT P5-3.01 WATER RISER DIAGRAM, A | | | BACKFLOW IS REQUIRED, AND WATER HAMMER | | | ARRESTORS REQUIRED BY 406.9 SHALL BE | | | LOCATED NEAR THE FIXTURE IN AN "EFFECT- | | | IVE RANGE" NOT AT THE TOP OF THE DROPS. | | | PER PDI-WH 201 AND MANUF. INSTALLATION | | | INSTRUCTIONS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|