| Plan Review Notes For Permit 02102206 |
| Permit Number |
02102206 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-03 00:00:00 | EDUCATIONAL BUILDING #5 | | | DENIED: | | | | | | PRIOVIDE INFORMATION ON THE CONDENSATE | | | DRAIN. INDICATE TERMINATION - AS PER | | | 2001 FBC(M) 307.2.1 (1) UNITS LARGER | | | THAN 6 TON SHALL DISCHARGE INTO STORM | | | DRAIN OR AN APPROVED DRYWELL. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS OR A SUPER- | | | VISORY SIGNAL AT A CONSTANTLY ATTENDED | | | LOCATION.NFPA 90A 4-4.4.3 & 4-4.4.2 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|