2002-12-03 00:00:00EDUCATIONAL BUILDING #5
 DENIED:
  
 PRIOVIDE INFORMATION ON THE CONDENSATE
 DRAIN. INDICATE TERMINATION - AS PER
 2001 FBC(M) 307.2.1 (1) UNITS LARGER
 THAN 6 TON SHALL DISCHARGE INTO STORM
 DRAIN OR AN APPROVED DRYWELL.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS OR A SUPER-
 VISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION.NFPA 90A 4-4.4.3 & 4-4.4.2
  