| Plan Review Notes For Permit 02102206 |
| Permit Number |
02102206 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-26 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS | | | NEED TO BE COMPLETED ON THE BOTTOM OF | | | 5L/A. PLEASE NOTE LOAD SHOWN ON 5MDP | | | DOES NOT CORRELATE WITH 5L/A. | | | | | | 2)NOTE: PLEASE CLARIFY MCB IN 5MDP | | | COMPLIES WITH 230-76/230-79. SHOWN AS | | | SHUNT TRIP, PLEASE NOTE, MUST HAVE A | | | MANUAL MEANS OF OPERATING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|