2002-11-26 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 NEED TO BE COMPLETED ON THE BOTTOM OF
 5L/A. PLEASE NOTE LOAD SHOWN ON 5MDP
 DOES NOT CORRELATE WITH 5L/A.
  
 2)NOTE: PLEASE CLARIFY MCB IN 5MDP
 COMPLIES WITH 230-76/230-79. SHOWN AS
 SHUNT TRIP, PLEASE NOTE, MUST HAVE A
 MANUAL MEANS OF OPERATING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  