2003-01-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4A SIGNED AND SEALED
 SURVEY DRAWING IS REQUIRED.
  
 2) FL. ADMIN. CODE 61G1-16.003EACH
 ARCHITECTURAL PLAN SHEET SHALL BE SIGNED
 PERSONALLY, NOT SIGNATURE STAMPED.
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING.
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT UPON THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING, EXTERIOR DOORS AND WINDOWS.
  
 8) FBC* TABLE 2306.1STRUCTURAL NOTES,
 SHEET STR-GN, PLYWOOD ROOF DECKING.THE
 PERIMETER ZONE AT THE GABLE END SHALL
 HAVE NAILS SPACED AT 4"O.C. MAXIMUM, TO
 A DISTANCE OF 5 FEET (NOT 24") FROM THE
 EDGE OF THE ROOF.
  
 9) STRUCTURAL NOTES, SHEET STR-GN, WOOD
 TRUSS NOTE 6.IT IS NOTED THAT THE
 TRUSS DESIGN ENGINEER IS TO PROVIDE THE
 WIND UPLIFT REACTIONS.THE PERMIT
 CANNOT BE ISSUED UNTIL THE REACTIONS ARE
 SPECIFIED ON THE PLANS FOR CROSS
 REFERENCE AGAINST THE PROPOSED TRUSS
 ANCHORS AND STRAPS.
  
 10) FBC 11-4.16.3SHEET A1-2.41, DETAIL
 8A THRU 10B.THE HEIGHT OF THE W.C.
 SEAT SHOULD BE 17" TO 19", NOT 1'-3".
  
 11) FBC 2405.2THE GLAZED PANELS
 ADJACENT DOORS 101.A, 113.A AND 121.A
 ARE IN A 'HAZARDOUS LOCATION' AND ARE
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 12) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499