| Plan Review Notes For Permit 02102205 |
| Permit Number |
02102205 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A4-2.1 KITCHEN/BREAK ROOM, SINK | | | SHALL COMPLY WITH SECTION 11-4.24 AND | | | ALL SUBSECTIONS. PLEASE PROVIDE DETAIL | | | 2) SHT P-4.201 RPZ BACK FLOW REQUIRED ON | | | WATER SERVICE. | | | 3) PLEASE PROVIDE A SANITARY RISER DIA- | | | GRAM AND A WATER RISER DIAGRAM. SHOW ALL | | | PIPE SIZES, ECT. ON SANT. RISER. | | | SHOW ALL PIPE SIZES AND WATER HAMMER | | | ARRESTORS REQUIRED FOR ALL QUICK CLOSING | | | VALVES PER 604.9. (WASH MACHINE, DISH | | | WASHER, ICE MACHINE). LOCATE NEAR FIX- | | | TURES IN AN "EFFECTIVE RANGE" NOT IN | | | CEILING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|