Plan Review Notes
Plan Review Notes For Permit 02102205
Permit Number 02102205
Review Stop P
Sequence Number 1
Notes
Date Text
2002-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A4-2.1 KITCHEN/BREAK ROOM, SINK
 SHALL COMPLY WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. PLEASE PROVIDE DETAIL
 2) SHT P-4.201 RPZ BACK FLOW REQUIRED ON
 WATER SERVICE.
 3) PLEASE PROVIDE A SANITARY RISER DIA-
 GRAM AND A WATER RISER DIAGRAM. SHOW ALL
 PIPE SIZES, ECT. ON SANT. RISER.
 SHOW ALL PIPE SIZES AND WATER HAMMER
 ARRESTORS REQUIRED FOR ALL QUICK CLOSING
 VALVES PER 604.9. (WASH MACHINE, DISH
 WASHER, ICE MACHINE). LOCATE NEAR FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT IN
 CEILING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377