| Plan Review Notes For Permit 02102205 |
| Permit Number |
02102205 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-12-02 00:00:00 | BUILDING #4 - VISTATION | | | DENIED: | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER 2001 FBC(M) TABLE 403.3, FOR ALL | | | AREAS, RESIDENTIAL & COMMON. | | | INDICATE DUCT SIZE, MATERIAL, LAYOUT | | | AND INTAKE LOCATION ON PLAN. | | | | | | 2.RETURN AIR REQUIRED FROM THE BEDROOM | | | AREA IN THE RESIDENTIAL SPACES. | | | 2001 FBC(M) 601.4. | | | | | | 3.PROVIDE INFORMATION ON THE DRYER | | | VENT.DUCT SIZE, MATERIAL, & | | | TERMINATION. | | | | | | 4.PROVIDE DETAIL FOR TOILET EXHAUST. | | | | | | 5.PLAN SHEET M4-2.01, EXHAUST FOR THE | | | BATHROOMS, JANITOR, AND ELECTRICAL | | | ROOMS NO DETAILS GIVEN AS TO SIZE, | | | MATERIAL OR TERMINATION.WILL DUCT | | | BE ENCLOSED IN A SHAFT THROUGH THE | | | ROOF OR OUT THE SIDE?PLEASE | | | CLARIFY. | | | | | | 6.VAV BOXES ARE IDENTIFIED ON PLAN | | | SHEET M4-2.01 BUT ARE NOT IDENTIFIED | | | ON THE SCHEDULE SHOWN ON M4-6.01. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|