| Plan Review Notes For Permit 02102205 |
| Permit Number |
02102205 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-26 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE MISSING ARC FAULT | | | PROTECTION FOR BEDROOM RECEPTS.210-12 | | | | | | 2)NOTE: PLEASE NOTE, MISSING REQ`D | | | SD`S PER NFPA-72 8-1 | | | | | | 3)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH PANEL SCHEDULES. | | | | | | 4)NOTE: PLEASE NOTE BATH CIRCTUIT(S) | | | PER 210-52D/210-11-C3 | | | | | | 5)NOTE: PLEASE NOTE KITCHEN COUNTERSPACE | | | OUTLETS TO MEET SPACING PER 210-52C. | | | | | | 6)NOTE: PLEASE NOTE, NO FIXTURE SCHEDULE | | | SUBMITTED. PLEASE CLARIFY IF LTS REQ`D | | | FOR EM ILLUMINATION MEET 700-16. | | | | | | 7)NOTE: PLEASE NOTE, PANELS AND LOAD | | | CALCULATIONS NEED TO BE DONE FOR A | | | REVIEW TO BE DONE. PLEASE COMPLETE | | | E4-4.01 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE NOTE, THERE MAY BE OTHER | | | COMMENTS WHEN PLANS ARE COMPLETED FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|