Plan Review Notes
Plan Review Notes For Permit 02102205
Permit Number 02102205
Review Stop B
Sequence Number 1
Notes
Date Text
2003-01-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4A SIGNED AND SEALED
 SURVEY DRAWING IS REQUIRED.
  
 2) FL. ADMIN. CODE 61G15-23.002THE
 FOUNDATION PLAN SHEET SHALL BE SIGNED,
 SEALED AND DATED.
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING.
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT UPON THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING, EXTERIOR DOORS AND WINDOWS.
  
 8) FBC* 104.2.1.2SUBMIT STRUCTURAL
 PLANS FOR THE SECOND FLOOR AND ROOF
 LAYOUT.
  
 9) FBC 311.2RESIDENTIAL OCCUPANCY
 CLASSIFICATION.DRAWING SHEET GN4-1
 STATES THE OCCUPANCY GROUP AS R3.IT IS
 ASSUMED THAT THIS DECISION IS BASED ON
 THE BUILDING ASSESSED AS 'ROOMING HOUSE
 (TRANSIENT)'.THIS IS NOT APPROPRIATE
 AS THE DEFINITION, IN SECTION 202, OF
 ROOMING HOUSE LIMITS THE BUILDING TO NOT
 MORE THAN FIVE GUEST ROOMS.THE CORRECT
 OCCUPANCY CLASSIFICATION WOULD BE R1.
  
 10) FBC 1004.2MINIMUM NUMBER OF EXITS.
 A MINIMUM OF TWO INDEPENDENT EXITS ARE
 REQUIRED FROM THE SECOND FLOOR BECAUSE
 THE BUILDING DOES NOT MEET THE
 CONDITIONS OF FBC 1026.1 (SINGLE EXIT),
 AND FBC 1026.1.2 DOES NOT APPLY (SEE
 PRECEDING COMMENT).AMEND THE PLANS TO
 SHOW TWO EXIT STAIRWAYS FROM THE SECOND
 FLOOR.
  
 11) FBC* 104.2.1.2SUBMIT A STAIRWAY
 LAYOUT DRAWING WITH DIMENSIONS/DETAILS
 OF THE STAIRS.
  
 12) SHEETS A4-2.1 AND A4-2.2.THE
 PARTITION LEGEND IS INCLUDED BUT NONE OF
 THE PARTITION TYPE REFERENCE MARKERS ARE
 SHOWN ON THE FLOOR LAYOUT.ALSO, THE
 'ARCHITECTURAL NOTES' AND 'DRAWING
 LEGEND' REFER TO SHEETS A4-10.1 AND
 A4-10.2 BUT THESE SHEETS ARE NOT
 INCLUDED WITH THE PLAN SET.
  
 13) FBC 2309.6SHEET A-11.02.ATTIC
 ACCESS PANELS APPEAR TO BE SHOWN ON THE
 PLAN, BUT THERE IS NO ANNOTATION TO
 CONFIRM THIS OR TO GIVE THE DIMENSIONS.
  
 14) FBC 11-4.9.4(2)SHEET A4-8.1, TYP.
 SIDE WALL RAILING DETAIL.THE HANDRAIL
 SHALL EXTEND AT LEAST 12" HORIZONTALLY
 BEYOND THE TOP RISER, AND SHALL
 CONTINUE TO SLOPE PAST THE BOTTOM RISER
 FOR A DISTANCE EQUAL TO THE WIDTH OF ONE
 TREAD AND THEN EXTEND A FURTHER 12"
 HORIZONTALLY AT THE BOTTOM.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499