Date Text
2003-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FLORIDA ADMIN. CODE
  
 1) PLANS STAMPED BY THE HEALTH DEPART-
 MENT SHALL BE SIGNED AND SEALED AND
 PLACED IN EACH SET OF PLANS IN THEIR
 PROPER ORDER. SECTION 104.2.2
 2) PREVIOUS COMMENT NOT ADDRESSED.
 CORRELATE PLANS FOR ROOF DRAINS AND
 ASSOCIATED PIPING. SHT P2-2.02 SHOWS ALL
 ROOF DRAINS AS 6". SHT P203.01 SHOWS 4"
 ROOF DRAIN AND 4" PIPING. SHT P2-4.3
 SHOWS A 4" ROOF DRAIN AND 6" PIPING.
 PLEASE CLAIRFY.
 3) ALL THREE SETS OF PLANS SHALL HAVE
 ALL SHEETS IN ORDER SIGNED, SEALED, DAT-
 ED, AND HAVE ALL INFORMATION REQUIRED IN
 TITLE BLOCK. SEE ATTACHED SHEETS FOR THE
 ARCHITECT AND ENGINEER. SECTIONS
 61G-15.002 AND 61G1-16.003/004
  