| Plan Review Notes For Permit 02102203 |
| Permit Number |
02102203 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2003-10-15 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FLORIDA ADMIN. CODE | | | | | | 1) PLANS STAMPED BY THE HEALTH DEPART- | | | MENT SHALL BE SIGNED AND SEALED AND | | | PLACED IN EACH SET OF PLANS IN THEIR | | | PROPER ORDER. SECTION 104.2.2 | | | 2) PREVIOUS COMMENT NOT ADDRESSED. | | | CORRELATE PLANS FOR ROOF DRAINS AND | | | ASSOCIATED PIPING. SHT P2-2.02 SHOWS ALL | | | ROOF DRAINS AS 6". SHT P203.01 SHOWS 4" | | | ROOF DRAIN AND 4" PIPING. SHT P2-4.3 | | | SHOWS A 4" ROOF DRAIN AND 6" PIPING. | | | PLEASE CLAIRFY. | | | 3) ALL THREE SETS OF PLANS SHALL HAVE | | | ALL SHEETS IN ORDER SIGNED, SEALED, DAT- | | | ED, AND HAVE ALL INFORMATION REQUIRED IN | | | TITLE BLOCK. SEE ATTACHED SHEETS FOR THE | | | ARCHITECT AND ENGINEER. SECTIONS | | | 61G-15.002 AND 61G1-16.003/004 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|