Date Text
2003-10-02 00:00:00************ UNSAT ******************
  
 THIS IS RESPONSE TO RESPONSE LETTER
 DATED 6/26/03
  
 PANEL 2LS/A HAS NOW BEEN CORRECTED.
 1)NOTE: PLEASE SEE CONDUCTORS SHOWN ON
 RISER DIAGRAM COMING FROM TRANSFORMER
 TO PANEL 2LS/A 4-1#8 ETC, CLARIFY SIZES
 INTO A 40A BRKR.
  
 2)NOTE: IT IS NOTED AND KNOWN THAT
 GENERATOR IS NOT IN A SEPARATE BLDG.
 THE NOTE AND CODES REFERENCE WAS FOR
 MEANS OF DISCONNECTING POWER COMING FROM
 GENERATOR TO THIS ACTIVITY BLDG.225.31
 PLEASE SEE THAT ATS APPEARS TO NOW SHOW
 A 400A MCB FOR THE MEANS OF DSIC.
 PLEASE SEE THAT THIS IS ON SECOND FLOOR
 AND NEEDS TO HAVE DISCONNECTING MEANS
 "GROUPED" WITH 2MDP.
 SHEET 3.01 IS NOW SUBMITTED AND THIS
 SHEET REFERENCES WHAT APPEARS TO BE
 TWO "SHUNT TRIP'S". PLEASE SEE THAT
 SHUNT TRIPS ARE NOT CONSIDERED TO BE
 "RATED" FOR THE LOAD SERVED. 230.76 AND
 230.79.
  
 3)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B). PLEASE SEE THAT WITH
 RESPECT TO DESIGN PROFESSIONAL(S) A
 4X FEE WILL BE ACCESSED FOR THE PORTION
 ATTRIBUTED TO PLAN REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]