| 2003-05-14 00:00:00 | ************* UNSAT ************** |
| | |
| | **PLEASE NOTE, THIS IS THE THIRD REVIEW |
| | WITH SOME OF THE SAME COMMENTS NOT |
| | ADDRESSED? LETTER WAS ATTACHED IN REF. |
| | TO FS 553.80(2)(B) WITH RESPECT TO |
| | DESIGNERS OF RECORD. |
| | |
| | A RESPONSE LETTER FROM OCI DATED |
| | 4TH FEBUARY 2003WAS FOUND IN SUBMITTAL |
| | PACKAGE. AN ELECTRICAL REVIEW WAS ALSO |
| | DONE ON 3/27/03 AND NOTES MENTIONS THAT |
| | NOTES FROM FIRST REVIEW DATED 11/26/02 |
| | WERE NOT ADDRESSED. |
| | PLEASE SEE THE FOLLOWING AND NOTE, SOMES |
| | NOTES HAVE NOT BEEN ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE PANEL 2LS/A, SHOWN |
| | AS 277/480V? HOW IS THIS THE LOADSIDE |
| | OF A STEPDOWN TRANSFORMER BEING FED |
| | FROM 277/480V/120/208V? |
| | |
| | 2)NOTE: PLEASE SEE RESPONSE FOR MEANS |
| | OF DISCONNECTING POWER FROM A ONE BLDG |
| | FEEDING TO ANOTHER. 225-31 A SHUNT TRIP |
| | HAS BEEN ADDED AT GENERATOR? THIS IS NOT |
| | A MEANS OF DISC FOR FEEDERS COMING TO |
| | MAIN BLDG? 225-31/230-76/230-79 |
| | A RELATED NOTE: MEANS OF DISC FOR EM PWR |
| | FROM GENERATOR AT MAIN BLDG, NOT SHOWN. |
| | GROUPING OF DISC`S PER 230-72, RATING |
| | OF DISC FOR LOAD SERVED AND MANUAL MEANS |
| | REQ`D UNDER 230-76/230-79. |
| | |
| | 3)NOTE: PLEASE SEE RESPONSE LETTER, |
| | A COUPLE OF THE RESPONSES MENTION TO |
| | SEE E-3.01 FOR DETAIL? PLEASE CLARIFY? |
| | THIS SHEET IS NOT IN SETS? |
| | |
| | PLEAS SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED |
| | SHEETS AND INSERT NEW SHEETS FOR |
| | COMPLETE SETS FOR STAMPING AND REVIEW. |
| | ONCE AGAIN, IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |