Plan Review Notes
Plan Review Notes For Permit 02102203
Permit Number 02102203
Review Stop E
Sequence Number 3
Notes
Date Text
2003-05-14 00:00:00************* UNSAT **************
  
 **PLEASE NOTE, THIS IS THE THIRD REVIEW
 WITH SOME OF THE SAME COMMENTS NOT
 ADDRESSED? LETTER WAS ATTACHED IN REF.
 TO FS 553.80(2)(B) WITH RESPECT TO
 DESIGNERS OF RECORD.
  
 A RESPONSE LETTER FROM OCI DATED
 4TH FEBUARY 2003WAS FOUND IN SUBMITTAL
 PACKAGE. AN ELECTRICAL REVIEW WAS ALSO
 DONE ON 3/27/03 AND NOTES MENTIONS THAT
 NOTES FROM FIRST REVIEW DATED 11/26/02
 WERE NOT ADDRESSED.
 PLEASE SEE THE FOLLOWING AND NOTE, SOMES
 NOTES HAVE NOT BEEN ADDRESSED.
  
 1)NOTE: PLEASE SEE PANEL 2LS/A, SHOWN
 AS 277/480V? HOW IS THIS THE LOADSIDE
 OF A STEPDOWN TRANSFORMER BEING FED
 FROM 277/480V/120/208V?
  
 2)NOTE: PLEASE SEE RESPONSE FOR MEANS
 OF DISCONNECTING POWER FROM A ONE BLDG
 FEEDING TO ANOTHER. 225-31 A SHUNT TRIP
 HAS BEEN ADDED AT GENERATOR? THIS IS NOT
 A MEANS OF DISC FOR FEEDERS COMING TO
 MAIN BLDG? 225-31/230-76/230-79
 A RELATED NOTE: MEANS OF DISC FOR EM PWR
 FROM GENERATOR AT MAIN BLDG, NOT SHOWN.
 GROUPING OF DISC`S PER 230-72, RATING
 OF DISC FOR LOAD SERVED AND MANUAL MEANS
 REQ`D UNDER 230-76/230-79.
  
 3)NOTE: PLEASE SEE RESPONSE LETTER,
 A COUPLE OF THE RESPONSES MENTION TO
 SEE E-3.01 FOR DETAIL? PLEASE CLARIFY?
 THIS SHEET IS NOT IN SETS?
  
 PLEAS SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE TAKE OUT ANY OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS FOR
 COMPLETE SETS FOR STAMPING AND REVIEW.
 ONCE AGAIN, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]