2003-03-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) ROUTE PLANS FROM THE PALM BEACH CTY
 HEALTH DEPT ARE NOT SIGNED AND SEALED.
 PLEASE SIGN AND SEAL PLANS AND STAMP FOR
 HEALTH DEPT APPROVAL ONLY OR MAKE ALL
 CORRECTIONS REQUIRED FROM ALL PLAN
 REVIEWS AND INSERT THOSE SHEETS INTO
 EACH SET FOR REVIEW.
 2) SHT A2-2.2 ROOF CALCULATIONS, GUTTERS
 FOR ALL ROOFS. PLEASE PROVIDE HORIZONTAL
 DETAIL FOR GUTTER. SHOW SLOPE FOR EACH
 SECTION, (MIN. 2% PER TABLE 1106.6), AND
 SHOW HOW MUCH OF THE GUTTER IS DRAINED
 TO EACH DOWNSPOUT.
 3) SHT A2-2.2 PLEASE PROVIDE CALCULATION
 FOR LOWER ROOF NOT ADDRESSED. SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING THE
 PARAPET WALLS. SHOW AREA FROM ROOF "B"
 THAT DRAINS ONTO LOWER ROOF IN CALCULAT-
 IONS. INDICATE HOW THE 2 SCUPPERS WILL
 DRAIN THE ROOF IN AN EMERGENCY.
 4) SHT P2-2.01 FROM PREVIOUS REVIEW,
 RESPONSE, (#6) INDICATES THAT A FLOOR
 SINK WAS PROVIDED, BUT THE DRAIN WAS
 DELETED ON REVISED SHEET P2-2.01. PLEASE
 CLAIRFY.
 5) EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. MANUAL AND
 UNION SHALL ALSO BE LOCATED BELOW CEIL-
 ING. MANUAL VALVE AND UNION SHALL BE
 BELOW CEILING ALSO
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377