| Plan Review Notes For Permit 02102203 |
| Permit Number |
02102203 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-04-04 00:00:00 | ADDITIONAL PERMITS REQUIRED: | | | | | | HOOD - PLAN SUBMITTED W/BUILDING PERMIT | | | FIRE SUPPRESSION - PLANS SUBMITTED | | | W/BUILDING PERMIT | | | WALK-IN COOLER/FREEZER - PROVIDE | | | MANUFACTURER SUBMITTAL DATA W/PERMIT | | | APPLICATION. | | | | | | GREASE DUCT: | | | 1. MATERIALS SHALL COMPLY W/2001 FBC(M) | | | 506.3.3. | | | 2. 1/4" PER FT SLOPE PER FBC(M) 506.3.9. | | | 3. CLEARANCE TO COMBUSTIBLES SHALL BE NO | | | LESS THAN 18" PER FBC(M) 507.9. |
|