Plan Review Notes
Plan Review Notes For Permit 02102203
Permit Number 02102203
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2003-03-21 00:00:001) EXITS PROVIDED FOR DINING ROOM 123
 DO NOT APPEAR TO BE PROPERLY
 SEPARATED FROM ONE ANOTHER.
  
 2) PLEASE EXPLAIN OPEN STAIR # 1.
  
 3) LIFE SAFETY PLAN DOES NOT INDICATE
 ANY EMERGENCY LIGHTS IN THE GALLERY,
 BATHROOMS,MEZZANINE LEVEL,STORAGE ROOM,
 AND DINING ROOM. THE ELECTRICAL PLAN
 SHOWS DIFFERENT INFORMATION. ARE NIGHT
 LIGHTS SHOWN ON THE ELECTRICAL PLAN
 THE SAME AS EMERGENCY LIGHTS.
  
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD, DUCT AND EXTINGUISHING
 SYSTEMS PLANNED FOR INSTALLATION.
  
 5) REQUIRED DUCT SMOKE DETECTORS ARE
 TO BE CONNECTED TO THE BUILDING'S FIRE
 ALARM SYSTEM.
  
 6) IT APPEARS THAT SECURITY DEVICES ARE
 PRESENT ON EXIT DOORS. PLEASE REVIEW
 SPECIAL LOCKING ARRANGEMENTS OF THE 2000
 LIFE SAFETY CODE, SECTION 7. PLEASE
 PROVIDE APPROPRIATE CODE SECTIONS ON THE
 PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910