| Plan Review Notes For Permit 02102203 |
| Permit Number |
02102203 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-03-27 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: ORIG NOTES ASKED TO SHOW | | | GROUNDING FOR TRANSFORMERS PER 250-30 | | | PLEASE CLARIFY WHERE THIS IS SHOWN? | | | THERE IS ONLY A NOTE MENTIONING GROUND | | | PER 250? | | | | | | 2)NOTE: PLEASE CLARIFY GROUNDING ELEC- | | | -TRODE SYSTEM, NOTE AT SERVICE SAYS TO | | | SEE DETAIL ON E-3.01, PLEASE SEE THAT | | | THIS SHEET WAS NOT SUBMITTED IN SET FOR | | | REVIEW? | | | | | | 3)NOTE: PLEASE SEE 230-76 AND 230-79 FOR | | | MEANS OF DISC REQ`D. SHUNT TRIPS ARE NOT | | | RATED FOR LOAD SERVED AND DO NOT COMPLY | | | W/ 230-72. PLEASE HAVE A DISC MEANS FOR | | | FEEDERS COMING TO BLDG/SEPARATE STUCTURE | | | 225-31 AND GROUPED PER 230-72/ 225-32 | | | | | | 4)NOTE: PLEASE SUBMIT/CLARIFY INFORMAT- | | | ION REQUESTED ON PREVIOUS REVIEW FOR | | | GENERATOR. SIZE /SPECS ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE MANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|