| 2003-04-23 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 1/13/03: |
| | |
| | 1) FBC* 105.13.1SPECIAL INSPECTOR.A |
| | STRUCTURAL INSPECTION PLAN MUST BE |
| | SUBMITTED PRIOR TO THE ISSUANCE OF A |
| | BUILDING PERMIT FOR THE CONSTRUCTION OF |
| | A THRESHOLD BUILDING.A THRESHOLD |
| | BUILDING IS ANY BUILDING WHICH IS |
| | GREATER THAN THREE STORIES OR 50 FEET IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY |
| | OCCUPANCY WITH 5,000 SQFT AREA AND |
| | GREATER THAN 500 OCCUPANTS. |
| | |
| | 2) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC* 104.2.4SITE SURVEY.A SIGNED AND |
| | SEALED SURVEY DRAWING PREPARED BY A |
| | QUALIFIED SURVEYOR IS REQUIRED (REF: |
| | 472.025(1) FL. STATUTES.). THE SUBMITTED |
| | SURVEY SHEET IS FOR A DELRAY BEACH |
| | LOCATION (???). |
| | |
| | 4) INFORMATIVE: |
| | A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 5) INFORMATIVE: |
| | IMPACT FEES MUST BE PAID TO PALM BEACH |
| | COUNTY, THE PLANS STAMPED BY THEM AND A |
| | COPY OF THE RECEIPT SUBMITTED TO THE |
| | CITY OF WEST PALM BEACH CONSTRUCTION |
| | SERVICES DEPARTMENT BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED. |
| | |
| | 6) FBC 11-4.1.2THE BUILDING SHALL BE |
| | SERVED BY AT LEAST ONE ACCESSIBLE ROUTE |
| | FROM THE ACCESSIBLE PARKING AND BUS STOP |
| | ACCEPTABILITY OF THESE PLANS IS |
| | CONTINGENT UPON THE CIVIL/SITE PLANS, |
| | PERMIT# 02102208, BEING PERMITTED. |
| | |
| | 7) THIS COMMENT HAS NOT BEEN ADDRESSED. |
| | FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 8) PRODUCT APPROVALS: DOOR, WINDOW, ROOF |
| | (A) ASPHALT SHINGLE PRODUCT APPROVAL |
| | NOA# 00-0105.02 EXPIRED ON 4/22/03. |
| | SUBMIT A VALID PRODUCT APPROVAL. |
| | (B) THE SUBMITTED COPY OF STEELCRAFT |
| | MANUF. 98/99 RIM EXIT STEEL DOOR PRODUCT |
| | APPROVAL NOA# 01-1203.11 IS MISSING TEXT |
| | SHEETS 2 AND 3 (SPECIFIC AND GENERAL |
| | CONDITIONS), AND SOME OF THE DRAWING |
| | SHEETS.SUBMIT A COMPLETE PRODUCT |
| | APPROVAL. |
| | (C) THE SUBMITTED COPY OF STEELCRAFT |
| | MANUF. F, M FRAME STEEL DOOR PRODUCT |
| | APPROVAL NOA# 01-0129.12 IS MISSING TEXT |
| | SHEETS 2 AND 3 (SPECIFIC AND GENERAL |
| | CONDITIONS), AND SOME OF THE DRAWING |
| | SHEETS.SUBMIT A COMPLETE PRODUCT |
| | APPROVAL. |
| | (D) NOT USED |
| | (E) THE DRAWING SHEETS OF THE SUBMITTED |
| | COPIES OF ARCH ALUMINUM STOREFRONT DOOR |
| | PRODUCT APPR. NOA# 01-0919.02 ARE POORLY |
| | REPRODUCED.SUBMIT LEGIBLE COPIES. |
| | COPIES OF MIAMI-DADE PRODUCT APPROVALS |
| | CAN BE PRINTED FROM THEIR WEBSITE,WWW. |
| | MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM |
| | (F) THE SUBMITTED 2 PAGE COPY EXTRACT OF |
| | THE 48 PAGE GAF MODIFIED BITUMEN ROOF |
| | PRODUCT APPROVAL NOA# 00-0331.09 DOES |
| | NOT INCLUDE A STATEMENT OF THE MAXIMUM |
| | DESIGN PRESSURE AND STATES THAT "ALL |
| | GENERAL AND SYSTEM LIMITATIONS SHALL |
| | APPLY".SUBMIT COPIES OF THE SHEETS |
| | WHICH STATE THE GENERAL AND SYSTEM |
| | LIMITATIONS AND THE MAX DESIGN PRESSURE. |
| | COPIES OF MIAMI-DADE PRODUCT APPROVALS |
| | CAN BE PRINTED FROM THEIR WEBSITE,WWW. |
| | MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM |
| | (G) SHEET A2-5.1, WEST ELEVATION.DOORS |
| | 108A AND 108B INCORPORATE GLAZED LITES |
| | ABOVE, GIVING AN OVERALL HEIGHT IN |
| | EXCESS OF 10 FT.THE DOOR SCHEDULE |
| | (SHEET A2-10.1) DOES NOT REFLECT THIS. |
| | ALSO THE OVERALL HEIGHT IS OUTSIDE THE |
| | SCOPE OF THE SUBMITTED ARCH ALUMINUM |
| | STOREFRONT DOOR PRODUCT APPROVAL |
| | NOA# 01-0919.02.SUBMIT AN APPROPRIATE |
| | DOOR PRODUCT APPROVAL OR A STRUCTURAL |
| | MULLION PRODCT APPROVAL. |
| | |
| | 9) THIS COMMENT HAS NOT BEEN PROPERLY |
| | ADDRESSED.FBC 1403.9 LIMITS RIGID |
| | VINYL SIDING TO BUILDINGS OF TYPE VI |
| | CONSTRUCTION ONLY.THIS BUILDING |
| | CANNOT BE TYPE VI AS THE OCCUPANCY CLASS |
| | AND AREA ARE OUTSIDE THE ACCEPTANCE |
| | CRITERIA (SEE COMMENT 13, BELOW).AN |
| | ALTERNATIVE TYPE OF SIDING THAT WOULD BE |
| | ACCEPTABLE IS FIBER-CEMENT SIDING |
| | (HARDIPLANK OR SIMILAR).AMEND NOTE 2 |
| | ON ELEVATION SHEETS A2-5.1 AND A2-5.2. |
| | |
| | 10) INFORMATIVE: |
| | STEEL ROOF TRUSS ANCHORING.G.D KLIEGER |
| | RESPONSE IS NOTED.ALL STRUCTURAL SHOP |
| | DRAWINGS SHALL BE REVIEWED AND STAMPED |
| | BY THE ENGINEER OF RECORD PRIOR TO |
| | SUBMITTAL TO WPB CONSTRUCTION SVCS DEPT. |
| | |
| | 13) FBC TABLE 500FROM GBS ARCHITECTURE |
| | COMMENT RESPONSE LETTER DATED 3-13-03, |
| | IT IS NOTED THAT THE OCCUPANCY LOAD HAS |
| | INCREASED AND THE PROPOSED CONSTRUCTION |
| | TYPE AND OCCUPANCY CLASS WERE REVISED TO |
| | TYPE VI CONSTRUCTION AND A-1 LARGE |
| | ASSEMBLY OCCUPANCY RESPECTIVELY. TYPE VI |
| | (WOOD) CONSTRUCTION FOR LARGE ASSEMBLY |
| | OCCUPANCY IS NOT PERMITTED BY TABLE 500. |
| | THE "MAX. NUMBER OF STORIES" FOR THAT |
| | COMBINATION IS SHOWN IN THE TABLE AS "0" |
| | IF THERE WERE NO RESTRICTIONS, AS STATED |
| | IN THE COMMENT RESPONSE LETTER, THE |
| | TABLE ENTRY WOULD BE NL (I.E. NO LIMIT). |
| | AMEND SHEET GN2-1. |
| | |
| | 14) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |
| | E-MAIL: [email protected] |