| 2002-12-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) ROUTE PLANS TO THE PALM BEACH COUNTY |
| | HEALTH UNIT, DIVISION OF ENVIRONMENTAL |
| | HEALTH, 901 EVERNIA ST W.P.B (561) 355- |
| | 3018 PRIOR TO RESUBMITTING FOR PLAN RE- |
| | VIEW. |
| | 2) PLEASE CONTACT RODNEY COMPO, ENVIRON- |
| | MENTAL COMPLIANCE @ (561) 837-4074 FOR |
| | SIZING OF GREASE TRAPS. WASTE ORDINANCE |
| | #2938-96 |
| | 3) SHT A2-2.2 ALL ROOF AREAS THAT HAVE |
| | PARAPET WALLS ON ALL SIDES SHALL HAVE A |
| | PRIMARY AND SECONDARY ROOF DRAIN. PLEASE |
| | SUBMIT CALCULATIONS FOR ALL ROOFS AND |
| | ALL PRIMARY AND SECONDARY DRAINS. |
| | 3A) PLEASE SUBMIT DETAILS FOR ALL ROOF |
| | SCUPPERS, GIVE HEIGHT & WIDTH. SHOW DE- |
| | TAILS FOR ALL GUTTERS PER TABLE 1106.6, |
| | GIVE SIZE OF ALL GUTTERS. |
| | 4) SHT K1.1 EQUIPMENT SCHEDULE, PLEASE |
| | SUBMIT MANUF. INFO. FOR WATER FILTER, |
| | ITEM #K6. SHALL BE "NSF" COMPLIANT. |
| | 5) SHT KP1.4 PLUMBING LEGEND, ITEM P-11, |
| | SAFE WASTE NOT APPROVED. ALL INDIRECT |
| | WASTE TO DRAIN INTO A FLOOR SINK. SECT. |
| | 802.3 |
| | 6) SHT P2-2.01 3" FUNNEL DRAIN NOT APP- |
| | ROVED. FLOOR SINK REQUIRED. (DINNING |
| | AREA) |
| | 7) SHT P2-3.01 DETAIL B/P2-301, RAIN |
| | WATER RUNS FROM 8" TO 6" THEN BACK TO |
| | 8" PIPE. PLEASE CLAIRFY. |
| | 8) SHT P2-4.01 GREASE LINE (RISER), SAFE |
| | WASTE NOT APPROVED AT JANITOR SINK - |
| | FLOOR DRAIN. PLEASE TIE FLOOR DRAIN |
| | DOWN STREAM OF JANITOR SINK. |
| | 9) SHT P2-4.01 GREASE LINE (RISER), FUN- |
| | NEL DRAIN NOT APPROVED, FLOOR SINK REQ- |
| | UIRED FOR ALL INDIRECT WASTE. 802.3 |
| | 10) SHT P2-4.01 AND SHT P2-2.01, DRAIN |
| | FROM THE DISHWASHER SHALL NOT DRAIN INTO |
| | GREASE LINE. PER UTILITY DEPT ALL DISH- |
| | WASHERS SHALL DRAIN TO SANITARY. |
| | 11) SHT P2-4.02 WATER RISER DIAGRAM, |
| | BACKFLOW REQUIRED ON WATER SERVICE. |
| | ALL WATER HAMMER ARRESTORS SHALL BE |
| | LOCATED NEAR THE FIXTURE IN AN "EFFECT- |
| | IVE RANGE" NOT AT THE TOP OF DROPS. PER |
| | PDI-WH 201 AND MANUFACTURE INSTRUCTIONS. |
| | 12 FOLLOWING ARE COMMENTS RELATING TO |
| | THE GAS SYSTEM. |
| | A. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 |
| | FUEL GAS CODE SEC. 402.2 |
| | C. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | D) SOLENOID VALVE SHALL BE APPROVED FOR |
| | OUTDOOR USE. PLEASE SUBMIT MANUFACTURE |
| | INFORMATION AND INSTALLATION INSTRUCTION |
| | A SHUT OFF VALVE AND UNION ARE REQUIRED |
| | UPSTREAM OF THE SOLENOID VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |