2002-12-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) ROUTE PLANS TO THE PALM BEACH COUNTY
 HEALTH UNIT, DIVISION OF ENVIRONMENTAL
 HEALTH, 901 EVERNIA ST W.P.B (561) 355-
 3018 PRIOR TO RESUBMITTING FOR PLAN RE-
 VIEW.
 2) PLEASE CONTACT RODNEY COMPO, ENVIRON-
 MENTAL COMPLIANCE @ (561) 837-4074 FOR
 SIZING OF GREASE TRAPS. WASTE ORDINANCE
 #2938-96
 3) SHT A2-2.2 ALL ROOF AREAS THAT HAVE
 PARAPET WALLS ON ALL SIDES SHALL HAVE A
 PRIMARY AND SECONDARY ROOF DRAIN. PLEASE
 SUBMIT CALCULATIONS FOR ALL ROOFS AND
 ALL PRIMARY AND SECONDARY DRAINS.
 3A) PLEASE SUBMIT DETAILS FOR ALL ROOF
 SCUPPERS, GIVE HEIGHT & WIDTH. SHOW DE-
 TAILS FOR ALL GUTTERS PER TABLE 1106.6,
 GIVE SIZE OF ALL GUTTERS.
 4) SHT K1.1 EQUIPMENT SCHEDULE, PLEASE
 SUBMIT MANUF. INFO. FOR WATER FILTER,
 ITEM #K6. SHALL BE "NSF" COMPLIANT.
 5) SHT KP1.4 PLUMBING LEGEND, ITEM P-11,
 SAFE WASTE NOT APPROVED. ALL INDIRECT
 WASTE TO DRAIN INTO A FLOOR SINK. SECT.
 802.3
 6) SHT P2-2.01 3" FUNNEL DRAIN NOT APP-
 ROVED. FLOOR SINK REQUIRED. (DINNING
 AREA)
 7) SHT P2-3.01 DETAIL B/P2-301, RAIN
 WATER RUNS FROM 8" TO 6" THEN BACK TO
 8" PIPE. PLEASE CLAIRFY.
 8) SHT P2-4.01 GREASE LINE (RISER), SAFE
 WASTE NOT APPROVED AT JANITOR SINK -
 FLOOR DRAIN. PLEASE TIE FLOOR DRAIN
 DOWN STREAM OF JANITOR SINK.
 9) SHT P2-4.01 GREASE LINE (RISER), FUN-
 NEL DRAIN NOT APPROVED, FLOOR SINK REQ-
 UIRED FOR ALL INDIRECT WASTE. 802.3
 10) SHT P2-4.01 AND SHT P2-2.01, DRAIN
 FROM THE DISHWASHER SHALL NOT DRAIN INTO
 GREASE LINE. PER UTILITY DEPT ALL DISH-
 WASHERS SHALL DRAIN TO SANITARY.
 11) SHT P2-4.02 WATER RISER DIAGRAM,
 BACKFLOW REQUIRED ON WATER SERVICE.
 ALL WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" NOT AT THE TOP OF DROPS. PER
 PDI-WH 201 AND MANUFACTURE INSTRUCTIONS.
 12 FOLLOWING ARE COMMENTS RELATING TO
 THE GAS SYSTEM.
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 D) SOLENOID VALVE SHALL BE APPROVED FOR
 OUTDOOR USE. PLEASE SUBMIT MANUFACTURE
 INFORMATION AND INSTALLATION INSTRUCTION
 A SHUT OFF VALVE AND UNION ARE REQUIRED
 UPSTREAM OF THE SOLENOID VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377