2002-12-03 00:00:00ACTIVITIES BUILDING #2
 DENIED:
  
 1) PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 2001 FBC(M) 501.4.
  
 2) PLANS ARE VAGUE AS TO ACCESS FOR THE
 EQUIPMENT LOCATED ON THE ROOF.PLAN
 SHEETS A2-7.1, A2-9.1, & ID-1 SHOW
 ACCESS TO THE EQUIPMENT LOCATED ON THE
 ROOF ABOVE THEKITCHEN/DINING AREA.
 CLARIFY ACCESS TO THE REST OF EQUIPMENT
 LOCATED ON THE OTHER ROOF AREAS.PLEASE
 NOTE, ACCESS TO EQUIPMENT LOCATED ON THE
 ROOF SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30".
  
 3) PLEASE NOTE, PLAN SHEET M2-5.01
 DETAIL #7, "COND. DRAINS SLOPE TO ROOF
 DRAIN OR DISCHARGE ON ROOF" - CONDENSATE
 SHALL NOT DISCHARGE ONTO THE ROOF.
  
 4) ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION & WALK-IN COOLER/FREEZER
  
 A) PROVIDE MANUFACTURER SUBMITTAL AND
 INSTALLATION INSTRUCTIONS FOR THE WALK
 IN COOLER & FREEZER WITH PERMIT THE
 PERMIT APPLICATION.
  
 B) PROVIDE SUBMITTAL DATA ON ANY FIRE
 WRAP OR SHAFTS (IF APPLICABLE) WITH
 PERMIT APPLICATION.
  
 C) AS PER NFPA 96 4-8.2.1 (E), A
 HINGED UPBLAST FAN WITH FLEXIBLE
 WEATHER PROOF ELECTRICAL CABLE SHALL
 BE USED. PLAN SHEET M2-5.02 INDICATES
 HIGNED FAN AS AN OPTION.
  
 D) AIR VELOCITY WITHIN THE DUCT SYSTEM
 SHALL BE NOT LESS THAN 1,500 FPM & NOT
 GREATER THAN 2,500 FPM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.