| 2002-12-03 00:00:00 | ACTIVITIES BUILDING #2 |
| | DENIED: |
| | |
| | 1) PROVIDE AIR BALANCE SCHEDULE SHOWING |
| | COMPLIANCE WITH 2001 FBC(M) 501.4. |
| | |
| | 2) PLANS ARE VAGUE AS TO ACCESS FOR THE |
| | EQUIPMENT LOCATED ON THE ROOF.PLAN |
| | SHEETS A2-7.1, A2-9.1, & ID-1 SHOW |
| | ACCESS TO THE EQUIPMENT LOCATED ON THE |
| | ROOF ABOVE THEKITCHEN/DINING AREA. |
| | CLARIFY ACCESS TO THE REST OF EQUIPMENT |
| | LOCATED ON THE OTHER ROOF AREAS.PLEASE |
| | NOTE, ACCESS TO EQUIPMENT LOCATED ON THE |
| | ROOF SHALL NOT REQUIRE CLIMBING OVER |
| | OBSTRUCTIONS GREATER THAN 30". |
| | |
| | 3) PLEASE NOTE, PLAN SHEET M2-5.01 |
| | DETAIL #7, "COND. DRAINS SLOPE TO ROOF |
| | DRAIN OR DISCHARGE ON ROOF" - CONDENSATE |
| | SHALL NOT DISCHARGE ONTO THE ROOF. |
| | |
| | 4) ADDITIONAL PERMITS REQUIRED FOR HOOD, |
| | FIRE SUPRESSION & WALK-IN COOLER/FREEZER |
| | |
| | A) PROVIDE MANUFACTURER SUBMITTAL AND |
| | INSTALLATION INSTRUCTIONS FOR THE WALK |
| | IN COOLER & FREEZER WITH PERMIT THE |
| | PERMIT APPLICATION. |
| | |
| | B) PROVIDE SUBMITTAL DATA ON ANY FIRE |
| | WRAP OR SHAFTS (IF APPLICABLE) WITH |
| | PERMIT APPLICATION. |
| | |
| | C) AS PER NFPA 96 4-8.2.1 (E), A |
| | HINGED UPBLAST FAN WITH FLEXIBLE |
| | WEATHER PROOF ELECTRICAL CABLE SHALL |
| | BE USED. PLAN SHEET M2-5.02 INDICATES |
| | HIGNED FAN AS AN OPTION. |
| | |
| | D) AIR VELOCITY WITHIN THE DUCT SYSTEM |
| | SHALL BE NOT LESS THAN 1,500 FPM & NOT |
| | GREATER THAN 2,500 FPM. |
| | |