| Plan Review Notes For Permit 02102203 |
| Permit Number |
02102203 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-01-23 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | | | | 2) SUITABLE ROADS ARE TO BE PROVIDED | | | FOR FIRE AND PARAMEDICAL EQUIPMENT | | | DURING CONSTRUCTION. | | | | | | 3) PLEASE PROVIDE A LIFE SAFETY PLAN | | | FOR THE BUILDING. | | | | | | 4) WHAT WILL THE MEZZANINE BE USED FOR. | | | | | | 5) WHY IS STAIR # 1 OPEN. | | | | | | 6) BUILDING ADDRESS REQUIRED. | | | | | | 7) A KNOX-BOX WILL BE REQUIRED. | | | | | | 8) PLEASE INDICATE HANDICAPPED SEATING. | | | | | | 9) ONLY THREE LABELED FIRE DOORS ARE | | | SHOWN ON DOOR SCHEDULE. PLEASE VERIFY | | | THIS. | | | | | | 10) COULD NOT LOCATE ANY EMERGENCY EXIT | | | LIGHTS ON MEZZANINE LEVEL. | | | | | | 11) NO SMOKE DETECTOR IN ELECTRICAL ROOM | | | 113, WHERE THE FACP IS LOCATED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|