2003-01-23 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO,DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 3) PLEASE PROVIDE A LIFE SAFETY PLAN
 FOR THE BUILDING.
  
 4) WHAT WILL THE MEZZANINE BE USED FOR.
  
 5) WHY IS STAIR # 1 OPEN.
  
 6) BUILDING ADDRESS REQUIRED.
  
 7) A KNOX-BOX WILL BE REQUIRED.
  
 8) PLEASE INDICATE HANDICAPPED SEATING.
  
 9) ONLY THREE LABELED FIRE DOORS ARE
 SHOWN ON DOOR SCHEDULE. PLEASE VERIFY
 THIS.
  
 10) COULD NOT LOCATE ANY EMERGENCY EXIT
 LIGHTS ON MEZZANINE LEVEL.
  
 11) NO SMOKE DETECTOR IN ELECTRICAL ROOM
 113, WHERE THE FACP IS LOCATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910