Plan Review Notes
Plan Review Notes For Permit 02102203
Permit Number 02102203
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-26 00:00:00****************** UNSAT **************
  
 PLEASE NOTE, THERE ARE MANY ITEMS ON
 RISER DIAGRAM AND PANEL SCHEDULES THAT
 ARE MISSING AND/OR DO NOT CORRELATE.
 PLEASE NOTE, A COMPLETE REVIEW CAN NOT
 BE ACCURATE AT THIS TIME.
  
 1)NOTE: PLEASE SEE 2MDP. SHOWN AS 100A
 MLO?
  
 2)NOTE: PLEASE NOTE, RISER DOES NOT
 SHOW HOW PANELS, 2EMF/A,2HLS/A,2EDP,
 ARE BEING FED FROM ON NORMAL POWER????
 RISER SHOWS THESE PANELS AND TRANSFOMER
 BEING ENERGIZED WHEN GENERATOR IS
 RUNNING> 215-5
  
 3)NOTE: PLEASE SHOW ALL GROUNDING FOR
 TRANSFORMERS PER 250-30.
  
 4)NOTE: PLEASE NOTE, MEANS OF DISC OF
 POWER COMING FROM GENERATOR TO BLDG.PER
 225-31. PLEASE NOTE, MEANS OF DISC TO
 BE GROUPED, 230-72,LABELED 230-2, RATING
 -S PER 230-76 AND 230-79.210-70 LOCAL
 AMENDMENTS.
  
 5)NOTE: PLEASE NOTE TAPPED CONDUCTORS
 FOR 2EMH/A AND 2KP. PLEASE NOTE BOTH
 PANELS HAVE NO MAINS. PLEASE ALSO SEE
 384-16 FOR LT AND APPL PANELS REQ`D TO
 HAVE MAINS.240-21
 PLEASE SEE PANEL SCHEDULE 2HLS/A NO
 LISTING FOR FEEDING TRANSFORMER TO
 2LS/A??
  
 6) NOTE: PLEASE NOTE, NO POWER SHOWN
 ON "NORMAL" LINE FOR ATS>
  
 7)NOTE: PLEASE NOTE, PLAN NOTE MENTIONS
 SEE GROUNDING DETAIL THIS SHEET?? PLEASE
 NOTE, NO DETAIL SHOWN.?? ALSO MENTIONS,
 TO BOND ALL SERVICES? PLEASE NOTE, ONLY
 ONE SHOWN??
  
 8)NOTE: PLEASE CLARIFY THAT MAIN IN
 2MDP MEETS 230-76/230-79.
  
 9)NOTE: PLEASE SUBMIT INFORMATION ON
 GENERATOR.SPECS ETC.
  
 10)NOTE: PLEASE NOTE LOADS SHOWN ON
 2MDP AND 2EDP DO NOT SEEM TO CALCULATED
 LOADS SHOWN ON PANEL SCHEDULE LOAD
 CALCS? PLEASE CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372