| Notes |
| Date |
Text |
| 2003-03-27 00:00:00 | ************* UNSAT ************ | | | | | | 1)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | SYSTEM. IT IS NOTED ON RISER THAT | | | GROUNDIGN ELECTRODE DETAIL IS ON SHEET | | | E3.01? PLEASE NOTE, NO SHEET 3.01 WAS | | | SUBMITTED FOR REVIEW.? | | | PLEASE ALSO SHOW GROUNDING DETAIL OR | | | NOTED WHERE TRANSFORMERS WILL BE | | | ATTACHED? BLDG STEEL/FOOTER? 250-30 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|