| 2002-12-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT A1-4.1 DETAIL #1 SHOWS 5'2" WIDTH |
| | FOR TOILET ROOM AND STALL. MINIMUM 5'3" |
| | IS REQUIRED FOR BOTH. |
| | 2) SHT A1-4.2 DETAIL #10A BREAK ROOM |
| | SINK SHALL COMPLY WITH SECTION 11-4.24, |
| | AND ALL SUBSECTIONS. PLEASE SHOW ON DE- |
| | TAIL KNEE CLEARANCE, CLEAR FLOOR SPACE, |
| | ECT. |
| | 3) SHT A1-4.3 DETAILS #5 & 9, PLEASE |
| | SHOW CLEAR FLOOR SPACE. IF FRONTAL APP- |
| | ROACH SHOW DETAILS FOR COMPLIANCE WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. IF |
| | PARALLEL APPROACH, SHOW ON PLANS. SINK |
| | TO BE CENTERED ON 48". |
| | 4) SHTS P1-2.02 & P1-3.01 ICE MAKER |
| | DRAIN, 2ND FLOOR PLUMBING PLAN AND SANT. |
| | RISER DIAGRAM, ALL INDIRECT WASTE SHALL |
| | DRAIN INTO A FLOOR SINK. SEC 802.3 |
| | 5) SHT P1-3.02 BACKFLOW REQUIRED ON |
| | WATER SERVICE TO ADMIN. BLDG. |
| | 6) SHT P1-3.02 WATER RISER DIAGRAM, |
| | WATER HAMMER ARRESTORS REQUIRED BY SEC. |
| | 604.9 SHALL BE LOCATED NEAR FIXTURES IN |
| | AN "EFFECTIVE RANGE" NOT AT TOP OF DROP |
| | AS SHOWN FOR 1ST FLOOR. PER PDI-WH 201 & |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | 7) SHT P1-4.01 WATER HEATER DETAIL/WATER |
| | HEATER SCHEDULE. W/H DETAIL SHOWN P/T & |
| | PAN DRAIN DRAINING TO JANITOR SINK, BUT |
| | W/H SCHEDULE SHOWS P/T & PAN DRAIN DRAIN |
| | ING INTO FLOOR DRAIN. (NOT APPROVED) |
| | PLEASE CLAIRFY. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |