Plan Review Notes
Plan Review Notes For Permit 02102198
Permit Number 02102198
Review Stop P
Sequence Number 1
Notes
Date Text
2002-12-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A1-4.1 DETAIL #1 SHOWS 5'2" WIDTH
 FOR TOILET ROOM AND STALL. MINIMUM 5'3"
 IS REQUIRED FOR BOTH.
 2) SHT A1-4.2 DETAIL #10A BREAK ROOM
 SINK SHALL COMPLY WITH SECTION 11-4.24,
 AND ALL SUBSECTIONS. PLEASE SHOW ON DE-
 TAIL KNEE CLEARANCE, CLEAR FLOOR SPACE,
 ECT.
 3) SHT A1-4.3 DETAILS #5 & 9, PLEASE
 SHOW CLEAR FLOOR SPACE. IF FRONTAL APP-
 ROACH SHOW DETAILS FOR COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. IF
 PARALLEL APPROACH, SHOW ON PLANS. SINK
 TO BE CENTERED ON 48".
 4) SHTS P1-2.02 & P1-3.01 ICE MAKER
 DRAIN, 2ND FLOOR PLUMBING PLAN AND SANT.
 RISER DIAGRAM, ALL INDIRECT WASTE SHALL
 DRAIN INTO A FLOOR SINK. SEC 802.3
 5) SHT P1-3.02 BACKFLOW REQUIRED ON
 WATER SERVICE TO ADMIN. BLDG.
 6) SHT P1-3.02 WATER RISER DIAGRAM,
 WATER HAMMER ARRESTORS REQUIRED BY SEC.
 604.9 SHALL BE LOCATED NEAR FIXTURES IN
 AN "EFFECTIVE RANGE" NOT AT TOP OF DROP
 AS SHOWN FOR 1ST FLOOR. PER PDI-WH 201 &
 MANUF. INSTALLATION INSTRUCTIONS.
 7) SHT P1-4.01 WATER HEATER DETAIL/WATER
 HEATER SCHEDULE. W/H DETAIL SHOWN P/T &
 PAN DRAIN DRAINING TO JANITOR SINK, BUT
 W/H SCHEDULE SHOWS P/T & PAN DRAIN DRAIN
 ING INTO FLOOR DRAIN. (NOT APPROVED)
 PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377