| Notes |
| Date |
Text |
| 2002-12-03 00:00:00 | ADMINISTRATION BUILDING #1 | | | DENIED: | | | | | | 1) PLAN SHEET M1-2.02 HVAC KEYNOTES #6, | | | "ROUTE 3/4" CONDENSATE DRAIN TERMINATE | | | AT RAIN LEADER."CONDENSATE SHALL BE | | | TO A DEDICATED LINE & TERMINATE INTO | | | STORM OUTSIDE OF BUILDING.PLEASE | | | CLARIFY. | | | | | | 2) FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS OR A SUPER- | | | VISORY SIGNAL AT A CONSTANTLY ATTENDED | | | LOCATION.NFPA 90A 4-4.4.3 & 4-4.4.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|