Plan Review Notes
Plan Review Notes For Permit 02102198
Permit Number 02102198
Review Stop M
Sequence Number 1
Notes
Date Text
2002-12-03 00:00:00ADMINISTRATION BUILDING #1
 DENIED:
  
 1) PLAN SHEET M1-2.02 HVAC KEYNOTES #6,
 "ROUTE 3/4" CONDENSATE DRAIN TERMINATE
 AT RAIN LEADER."CONDENSATE SHALL BE
 TO A DEDICATED LINE & TERMINATE INTO
 STORM OUTSIDE OF BUILDING.PLEASE
 CLARIFY.
  
 2) FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS OR A SUPER-
 VISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION.NFPA 90A 4-4.4.3 & 4-4.4.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.