| 2002-11-26 00:00:00 | ****************UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SHOW LOCATION OF SERVICE/ |
| | 1MDP.SHOWN ON RISER IN RM 126?? |
| | PLEASE NOTE, THIS IS CLARIFY DISTANCE |
| | FROM MDP TO PRIMARY SIDE OF TRANSFORMERS |
| | PLANS/LINE DIAGRAM DOES NOT SHOW HOW FAR |
| | AWAY.? TAPPED CONDUCTORS 240-21 |
| | |
| | 2)NOTE: PLEASE CLARIFY PANEL SCHEDULE |
| | FOR 1L/B? PLEASE NOTE THERE IS ANOTHER |
| | PANEL SCHEDULE SHOWN. MISPRINT? |
| | |
| | 3)NOTE: PLEASE NOTE, RISER DIAGRAM SHOWS |
| | THE "GUARDHOUSE" PANEL AS 120/240V AND |
| | BEING FROM MDP WHICH IS 277/480V? |
| | PLEASE CLARIFY. |
| | |
| | 4)NOTE: PLEASE SHOW GROUNDING ATTHE |
| | DEATCHED "GH". PER 250-32 |
| | |
| | 5)NOTE: PLEASE SHOW LOCATIONS FOR |
| | GROUNDING OF TRANSFORMERS PER 250-30. |
| | |
| | 6)NOTE: PLEASE SEE NOTE GROUNDING |
| | ELECTRODE SYSTEM BELOW MDP, NOTE MENTION |
| | -S, "SEE GROUNDING DETAIL THIS SHEET"?? |
| | PLEASE CLARIFY WHERE THIS DEATIL CAN BE |
| | FOUND. ALSO MENTIONS "ALL SERVICES TO |
| | BE BONDED TOGETHER? PLEASE NOTE, ONLY |
| | ONE SERVICE IS SHOWN. ?? |
| | |
| | 7)NOTE: PLEASE CLARIFY THE MDP HAS |
| | A MCB THE MEETS 230-76 AND 230-79. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |