2002-11-26 00:00:00****************UNSAT **************
  
 1)NOTE: PLEASE SHOW LOCATION OF SERVICE/
 1MDP.SHOWN ON RISER IN RM 126??
 PLEASE NOTE, THIS IS CLARIFY DISTANCE
 FROM MDP TO PRIMARY SIDE OF TRANSFORMERS
 PLANS/LINE DIAGRAM DOES NOT SHOW HOW FAR
 AWAY.? TAPPED CONDUCTORS 240-21
  
 2)NOTE: PLEASE CLARIFY PANEL SCHEDULE
 FOR 1L/B? PLEASE NOTE THERE IS ANOTHER
 PANEL SCHEDULE SHOWN. MISPRINT?
  
 3)NOTE: PLEASE NOTE, RISER DIAGRAM SHOWS
 THE "GUARDHOUSE" PANEL AS 120/240V AND
 BEING FROM MDP WHICH IS 277/480V?
 PLEASE CLARIFY.
  
 4)NOTE: PLEASE SHOW GROUNDING ATTHE
 DEATCHED "GH". PER 250-32
  
 5)NOTE: PLEASE SHOW LOCATIONS FOR
 GROUNDING OF TRANSFORMERS PER 250-30.
  
 6)NOTE: PLEASE SEE NOTE GROUNDING
 ELECTRODE SYSTEM BELOW MDP, NOTE MENTION
 -S, "SEE GROUNDING DETAIL THIS SHEET"??
 PLEASE CLARIFY WHERE THIS DEATIL CAN BE
 FOUND. ALSO MENTIONS "ALL SERVICES TO
 BE BONDED TOGETHER? PLEASE NOTE, ONLY
 ONE SERVICE IS SHOWN. ??
  
 7)NOTE: PLEASE CLARIFY THE MDP HAS
 A MCB THE MEETS 230-76 AND 230-79.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  