| 2003-01-08 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) FBC* 104.2.4A SIGNED AND SEALED |
| | SURVEY DRAWING IS REQUIRED. |
| | |
| | 2) FL. ADMIN. CODE 61G1-16.003EACH |
| | ARCHITECTURAL PLAN SHEET SHALL BE SIGNED |
| | PERSONALLY, NOT SIGNATURE STAMPED. |
| | |
| | 3) INFORMATIVE: |
| | A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 4) INFORMATIVE: |
| | IMPACT FEES MUST BE PAID TO PALM BEACH |
| | COUNTY, THE PLANS STAMPED BY THEM AND A |
| | COPY OF THE RECEIPT SUBMITTED TO THE |
| | CITY OF WEST PALM BEACH CONSTRUCTION |
| | SERVICES DEPARTMENT BEFORE A BUILDING |
| | PERMIT CAN BE ISSUED. |
| | |
| | 5) FBC 11-4.1.2THE BUILDING SHALL BE |
| | SERVED BY AT LEAST ONE ACCESSIBLE ROUTE |
| | FROM THE ACCESSIBLE PARKING. |
| | ACCEPTABILITY OF THESE PLANS IS |
| | CONTINGENT UPON THE CIVIL/SITE PLANS, |
| | PERMIT# 02102208, BEING PERMITTED. |
| | |
| | 6) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR THE |
| | ROOFING, EXTERIOR DOORS AND WINDOWS. |
| | |
| | 8) FBC 1403.9ELEVATION SHEETS A1-5.1 & |
| | A1-5.2.4" VINYL SIDING IS SPECIFIED IN |
| | NOTE 2.RIGID VINYL SIDING IS LIMITED |
| | TO TYPE VI CONSTRUCTION.FROM TABLE 500 |
| | THE AREA OF THIS BUILDING EXCEEDS THE |
| | ACCEPTANCE CRITERIA FOR TYPE VI |
| | CONSTRUCTION. |
| | |
| | 9) FBC* TABLE 2306.1STRUCTURAL NOTES, |
| | SHEET STR-GN, PLYWOOD ROOF DECKING.THE |
| | PERIMETER ZONE AT THE GABLE ENDS SHALL |
| | HAVE NAILS SPACED AT 4"O.C. MAXIMUM, TO |
| | A DISTANCE OF 5 FEET (NOT 24") FROM THE |
| | EDGE OF THE ROOF. |
| | |
| | 10) STRUCTURAL NOTES, SHEET STR-GN, WOOD |
| | TRUSS NOTE 6.IT IS NOTED THAT THE |
| | TRUSS DESIGN ENGINEER IS TO PROVIDE THE |
| | WIND UPLIFT REACTIONS.THE PERMIT |
| | CANNOT BE ISSUED UNTIL THE REACTIONS ARE |
| | SPECIFIED ON THE PLANS FOR CROSS |
| | REFERENCE AGAINST THE PROPOSED TRUSS |
| | ANCHORS AND STRAPS. |
| | |
| | 11) FBC 11-4.9.4(2)SHEET A1-8.1, TYP. |
| | SIDE WALL RAILING DETAIL (ALSO SHEET |
| | A1-9.1 STAIR 109/209 SECTION).THE |
| | HANDRAIL SHALL EXTEND AT LEAST 12" |
| | HORIZONTALLY BEYOND THE TOP RISER, AND |
| | SHALL CONTINUE TO SLOPE PAST THE BOTTOM |
| | RISER FOR A DISTANCE EQUAL TO THE WIDTH |
| | OF ONE TREAD AND THEN A FURTHER 12" |
| | HORIZONTALLY AT THE BOTTOM. |
| | |
| | 12) FBC 11-4.13.6MANEUVERING CLEARANCE |
| | AT DOORS.THE LEADING EDGE OF DOOR 202B |
| | SHOULD BE NO LESS THAN 18" AWAY FROM THE |
| | CORRIDOR WALL ON THE PULL SIDE OF THE |
| | DOOR. |
| | |
| | 13) FBC 11-4.16.3SHEET A1-2.41, DETAIL |
| | 5A AND SHEET A1-4.1, DETAIL 2A, 2B, 4A. |
| | THE HEIGHT OF THE W.C. SEAT SHOULD BE |
| | 17" TO 19", NOT 1'-3". |
| | |
| | 14) FBC 2405.2THE GLAZED PANEL AT HR |
| | RECEPTION IS WITHIN 24" OF DOOR 103. |
| | THIS IS A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).SUBMIT DETAILS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 15) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| | ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| | OLD SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHALL BE INCLUDED WITH THE |
| | RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |